MAINTENANCE REPORT 
 
In unusually dirty or dusty conditions, care must be taken to keep water heater cabinet door in place at all times. Failure to do so VOIDS 
WARRANTY! 
 
 
Allowing the water heater to operate with a dirty combustion chamber will hurt operation. Failure to clean the heat exchanger as needed 
by the installation location could result in water heater failure, property damage, personal injury, or death. Such product failures ARE 
NOT covered under warranty. 
 
The water heater requires minimal periodic maintenance under normal conditions. However, in unusually dirty or dusty conditions, 
periodic vacuuming of the cover to maintain visibility of the display and indicators is recommended. 
 
Periodic maintenance should be performed once a year by a qualified service technician to assure that all the equipment is operating 
safely and efficiently. The owner should make necessary arrangements with a qualified heating contractor for periodic maintenance of 
the water heater. Installer must also inform the owner that the lack of proper care and maintenance of the water heater may result in a 
hazardous condition. 
 
INSPECTION ACTIVITIES 
DATE LAST COMPLETED 
PIPING 
1
st
 YEAR 
2
nd
 YEAR 
3
rd
 YEAR 
4
th
 YEAR* 
Near water heater 
piping 
Check water heater and system piping for any sign of 
leakage. Leaking pipes could cause property damage. 
Make sure all piping is properly supported. Flush tankless 
heat exchanger annually (more in hard water conditions). 
See User’s Information manual for instructions. 
 
 
 
 
Vent 
Check condition of all vent pipes and joints. Ensure all 
vent piping is properly supported. Check for obstructions 
exhaust and intake termination points. 
 
 
 
 
Gas 
Check Gas piping, test for leaks and signs of aging. Make 
sure all pipes are properly supported. 
 
 
 
 
SYSTEM 
Visual 
Do a full visual inspection of all system components. 
 
 
 
 
Functional 
Test all functions of the system (Heat, Safeties) 
 
 
 
 
Temperatures 
Verify safe settings on water heater or Anti-Scald Valve 
 
 
 
 
Temperatures 
Verify programmed temperature settings 
 
 
 
 
ELECTRICAL 
Connections 
Check wire connections. Make sure they are tight. 
 
 
 
 
Smoke and CO 
detector 
Verify devices are installed and working properly. Change 
batteries if necessary. 
 
 
 
 
Circuit Breakers 
Check to see that the circuit breaker is clearly labeled. 
Exercise circuit breaker. 
 
 
 
 
Switch and Plug 
Verify ON/OFF switch and convenience plug are both 
functional 
 
 
 
 
CHAMBER/BURNER 
Combustion Chamber 
Check burner tube and combustion chamber coils. Clean 
according to maintenance section of manual. Vacuum 
combustion chamber. 
 
 
 
 
Spark Electrode 
Clean. Set gap at 1/8”. 
 
 
 
 
CONDENSATE 
Condensate Trap 
Clean debris from the condensate trap. Fill with clean 
water. 
 
 
 
 
Neutralizer 
Check condensate neutralizer. Replace if necessary. 
 
 
 
 
Condensate hose 
Disconnect condensate hose. Clean out dirt and re-install. 
(NOTE: Verify the flow of condensate, making sure that 
the hose is properly connected during final inspection.) 
 
 
 
 
GAS 
Pressure 
Measure incoming gas pressure (
3.5” to 14” W.C.) 
 
 
 
 
Pressure Drop 
Measure drop in pressure on light off (no more than 1” 
W.C.) 
 
 
 
 
Check gas pipe for 
leaks 
Check piping for leaks. Verify that all are properly 
supported. 
 
 
 
 
COMBUSTION 
CO/CO2 Levels 
Check CO and CO2 levels in Exhaust. Record at high and 
low fire. 
 
 
 
 
SAFETIES 
ECO (Energy Cut Out) 
Check continuity on Flue and Water ECO. Replace if 
corroded.