Westinghouse EPA (49 state) WH6500E Manual Do Proprietário

Página de 86
  
21
OPERATION
Using Westinghouse Power Cord
Use the extension cord chart to determine the size 
of the conductor for extension cord applications. 
Determine the distance of the generator to the 
appliance on the top line of the chart. Then select the 
rated amperage of the generator on the left side of the 
chart. Where the two meet is the size of the conductor 
required for the application.
The WCG25 power cord is connected to the generator 
at the 120/240 plug. The opposite end of the power 
cord is a fan tail receptacle with 2 green receptacles 
and 2 red receptacles. Each receptacle is rated at 
120 volts AC. To balance the load on the generator’s 
alternator, use the red and green identifiers on the fan 
tail receptacle. To keep the load balanced, connect 
the loads so that both color receptacles are used. An  
example is one in red and one in green. Do not connect 
2 in red and none in green, or 2 in green and none in 
red. If only one color receptacle is used with multiple 
loads, the alternator may experience an unbalanced 
load, causing undue vibration to generator.
1
2
Figure 13
1 -   Green  Dots
2 -  Red Dots
TRANSFER SWITCH 
CONNECTIONS
The Westinghouse generator is wired with the neutral 
bonded to ground. If you are connecting your generator 
to a transfer switch, the electrician must first determine 
what type transfer switch is being used. Transfer 
switches for this equipment are either two-pole or three-
pole types.
A two-pole transfer switch will not switch the neutral 
from the generator to the service panel. That means 
the generator will be grounded to the service panel. To 
use the generator with two-pole transfer switches, the 
electrician will need to change the neutral from bonded 
to floating. 
This is done by removing the jumper wire that connects 
the alternator ground to the alternator neutral. Remove 
the jumper wire and retighten the connections. Keep 
the jumper wire with the owner’s manual in case it is 
needed for future use when not connected to a transfer 
switch.
Figure 14