Damper installation 
continued
.  Read  and  apply  the  harness  plug  warning  label
(shown  above)  so  that  it  is  visible  after  installa-
tion.
.  Plug damper harness receptacle into damper harness
plug.
 Bypassing (jumpering) vent damper will
cause flue products such as carbon mon-
oxide to escape into the house. This will
cause severe personal injury or death.
 After boiler has operated once, if either
end  of  the  harness  is  disconnected,  the
system  safety  shutdown  will  occur.  The
boiler  will  not  operate  until  harness  is
reconnected.
Effikal  damper
 —  Damper  hold  open
switch must be in “Automatic Operation”
position for system to operate properly.
Minimum clearances to 
combustibles
Provide  a  minimum  of  ”  between  the  vent  damper
and any combustible material. (Provide a minimum of
” between jacket top and combustible ceiling.) See
EG • PEG • EGH Boiler manual for complete clearance
requirements.
Installation
 Do not modify draft hood or damper, or
make another connection between draft
hood and damper or boiler except as not-
ed below. This will void CSA certification
and will not be covered by Weil-McLain
warranty. Any changes will cause severe
personal  injury,  death,  or  substantial
property damage.
1.  Install  vent  damper  horizontally  or  vertically  as
shown in vent damper manufacturer’s instructions.
Vent damper must be installed so that it serves only
one boiler and so damper blade indicator is visible
to the user. See Figure 8.
.  Screws or rivets used to secure the vent damper to
the draft hood must not interfere with rotation of
the damper blade.
.  Install  damper  harness  between  damper  actuator
and knockout in jacket top panel. Use strain relief
connectors and locknuts to secure both ends of the
damper harness.
 Keep wiring harness clear of all hot sur-
faces.