Control module provides freeze-up protection when boiler 
water temperature drops below 45° F:
• Below 45° F, boiler circulator operates constantly.
• Below 37° F, boiler operates at low fire.
• Boiler and circulator turn off if boiler water temperature 
rises above 50° F.
This boiler control feature does not eliminate possibility 
of freezing. Installation must use recognized design, 
installation and maintenance practice to prevent freeze 
potential for boiler and system.
Supply Temperature Boost
• Outdoor reset operation (factory supplied, field installed 
outdoor sensor connected), boiler control automatically 
increases target outlet water temperature if call for 
heat exceeds 10 minutes.  
• At each 10 minutes of continuous call for heat, control 
module increases target temperature by 18°F.  Module 
continues increasing target temperature until it reaches 
value set in Parameter 4.
• When call for heat ends while target temperature is 
“boosted,” target temperature drops about 2°F for each 
minute thermostat is open.
Purpose of “Boosting”: If target temperature is too 
low, control “boosts” target temperature until supply water 
meets system needs.
Outdoor Reset Operation
Target temperature with outdoor reset: All boilers ship with 
outdoor temperature sensor. When sensor is installed (low 
voltage terminal strip terminals A1 and A2), boiler control 
regulates target outlet water temperature based on outside 
temperature. 
Set temperature curve by setting Parameter 4 to:
• ODT (outdoor design temperature for the area).
• ODT of 0°F or lower, set Parameter 4 to desired supply 
temperature at ODT.
• ODT above 0°F, set Parameter 4 to desired system 
temperature when outdoor temperature is 0°F.
Reset curve: See reset curve graph, shows how boiler 
control calculates target temperature.
• Outdoor temperature at or below 0°F, target 
temperature equals Parameter 4 and never higher.
• Outdoor temperature above 0°F, target temperature 
is reduced on a curve that would result in 60°F supply 
temperature at 70°F outdoor temperature.
Summer/winter switch option: Install summer/winter 
switch, if desired, to disable boiler (space heating) 
circulator during non-heating months. Connect switch 
across outdoor sensor terminals. When switch closes, boiler 
circulator is disabled and boiler operates only on call for 
DHW heating.
DHW Operation (option)
Control allows connection of DHW aquastat to low voltage 
terminal strip terminals DHW T1 and DHW T2. When 
DHW aquastat calls for heat, module shuts down boiler 
circulator activated DHW circulator and immediately sets 
target outlet water temperature to 180°F. This provides 
automatic priority heat allocation to indirect water heater 
for maximum response and recovery.  DHW circulator 
continues for 30.6 seconds after heating cycle to deliver 
heat.
3 - OPERATING INFORMATION
Target Outlet T
emperature, °F
Outside Temperature, °F
Outdoor Reset Target Temperature
210
50
70
60
50
40
30
20
10
0
-10
-20
70
90
110
130
150
170
160
190
120
Parameter 4 = 190°F
Parameter 4 = 150°F
Parameter 4 = 170°F
Reset Curve Calculations
Reset Curve Calculations   
Target Outlet T
emperature, °F
Outside Temperature, °F
Default Reset Curve
Outdoor Reset Target Temperature
210
50
70
60
50
40
30
20
10
0
-10
-20
70
90
110
130
150
170
160
190
180
120
Parameter 7 = 60°F
Parameter 4 = 180°F
Parameter 6 = 0°F
Default Reset Curve