Toshiba 48-1250 A Manual Do Utilizador

Página de 96
TOSHIBA- 27
TX  Series
   48 - 1250A
5.1.6 User I/O Configuration (Setpoint Page 6)
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range
Section
Tachometer  Scale Selection
Disabled
Enabled or Disabled
Manual Tach Scale 4.0 mA:
0 RPM
0 - 3600
Manual Tach Scale 20.0 mA:
2000 RPM
0 - 3600
Tach Accel Trip Mode Select
Disabled
Underspeed, Overspeed or Disabled
Tach Ramp Time
20 sec
1 - 120
Tach Underspeed Trip PT
1650 RPM
0-3600
Tach Overspeed Trip PT
1850 RPM
0 - 3600
Tach Accel Trip Delay
1 sec
1 - 60
Analog Output #1
RMS Current
Off,  RPM 0-3600,  Hottest Non-Stator RTD 0-
200°C, Hottest Stator RTD 
0 - 200°C, RMS Current 0 - 7500 A, % Motor 
Load 0 - 600%, kw 0 - 30000kw.
Analog Output #1 4mA:
0
0-65535
Analog Output #1 20mA:
250
0-65535
Analog Output #2
% Motor Load
Same As Analog Input #1
Analog Output #2 4mA:
0
0-1000%
Analog Output #2 20mA:
1000
0-1000%
User Programmable External 
Inputs
External Input #1
Disabled
Enabled or Disabled
Name Ext. Input #1
User Defined, up to 15 Characters
External Input #1
NO
Normally Open or Closed
External Input #1
0 sec
0-60 sec
External Input #2
Disabled
Enabled or Disabled
Name Ext. Input #2
User Defined, up to 15 Characters
External Input #2 Type
NO
Normally Open or Closed
External Input #2 Time Delay
0 sec
0-60 sec
Dual Ramp
Dual Ramp
Enabled or Disabled or Dual Ramp
Name Ext. Input #3
Dual Ramp
User Defined, up to 15 Characters
Dual Ramp Type
NO
Normally Open or Closed
Dual Ramp Time Delay
0 sec
0-60 sec
Thermostat
Enabled
Enabled or Disabled
Name Ext. Input #4
Thermostat
User Defined, up to 15 Characters
Thermostat Type
NC
Normally Open or Closed
Thermostat Time Delay
1 sec
0-60 sec
P