TOSHIBA- 37
TX  Series
   48 - 1250A
SP.3 Phase & Ground Settings (Setpoint Page 3)
(Security Level: 2)
Note:
Proper phase sequence must be observed when
connecting the input power. For example, phase A
must lead phase B, which in turn must lead phase
C by 120° respectively. If the phase rotation is not
correct, a fault light and the LCD display will
indicate the problem.
SP3.1
Imbalance Alarm Level:  This is an advance
warning of a phase imbalance problem.  The
problem may not be a fault in the motor, but merely
caused by imbalanced voltages.
• Imbalance Alarm Delay: The amount of time the
imbalance condition must exist before an alarm
occurs.
SP3.2
Imbalance Trip Level: This will trip the motor on
excessive phase imbalance.  The trip level should
be programmed to a higher value than the alarm
level.
• Imbalance Trip Delay: The amount of time the
imbalance condition must exist before a trip will
occur.
SP3.3
Undercurrent Alarm Level: Typically used to
warn of possible load loss, a coupling breaking or
other mechanical problems.
• Undercurrent Alarm Delay: The amount of time
the undercurrent condition must exist before an
alarm will occur.
SP3.4
Overcurrent  Alarm Level: Typically used to
indicate when the motor is overloaded.  This feature
can be used to either stop the feed to the
equipment or warn operators of an overload
condition.
• Overcurrent Alarm Delay: The amount of time
the overcurrent condition must exist before an
alarm will occur.
MENU
PAGE 3  PHASE &
GROUND SETTINGS
IMBALANCE ALARM
LEVEL:   15% FLA
Range: 5 - 30%, OFF
Increments of 1
(Hit DOWN ARROW two times)
IMBALANCE ALARM
DELAY:        1.5 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
IMBALANCE TRIP
LEVEL:  20%FLA
OVERCURRENT ALARM
LEVEL:   OFF
Range: 5 - 30%, OFF
Increments of 1
Range: 100 - 300%, OFF
Increments of 1
IMBALANCE TRIP
DELAY:   2.0 SEC.
OVERCURRENT ALARM
DELAY:   2.0 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
Range: 1.0 - 20.0 SEC., OFF
Increments of 0.1
OVERCURRENT TRIP
LEVEL:  OFF
PHASE LOSS TRIP
:   DISABLED
Range: 100 - 300%, OFF
Increments of 1
Options: Enabled or Disabled
OVERCURRENT TRIP
DELAY:   2.0 SEC.
PHASE LOSS TRIP
DELAY:         0.1 SEC.
Range: 1.0 - 20.0 SEC.
Increments of 0.1
Range: 0 - 20.0 SEC.
Increments of 0.1
UNDERCURRENT ALARM
LEVEL:       OFF
Range: 10 - 90%, OFF
Increments of 1
UNDERCURRENT ALARM
DELAY:   2.0 SEC.
Range: 1.0 - 60.0 SEC.
Increments of 0.1
PHASE ROTATION
DETECTION:  DISABLED
GROUND FAULT LOSET
TRIP LEVEL:   OFF
Options: Enabled or Disabled
Options: ABC, ACB
Range: 5 - 90%, OFF
Increments of 1
PHASE ROTATION
: ABC 
GROUND FAULT LOSET
TRIP DELAY: 0.5 SEC
Range: 1.0 - 20.0 SEC., OFF
Increments of 0.1
GROUND FAULT HISET
TRIP LEVEL:  OFF
Range: 5 - 90%, OFF
Increments of 1
GROUND FAULT HISET
TRIP DELAY:  0.008 SEC.
Range: 0.008 - 0.250 SEC.
Increments of 0.002
GROUND FAULT ALARM
LEVEL:  OFF
Range: 5 - 90%, OFF
Increments of 1
GROUND FAULT ALARM
DELAY:  0.1 SEC.
Range: 0.5 - 20.0 SEC.
Increments of 0.1
OVERVOLTAGE ALARM
LEVEL:     OFF
OVERVOLTAGE ALARM
DELAY:     1.0 SEC.
Range: 5 - 30%, OFF
Increments of 1
Range: 1.0 - 30.0 SEC.
Increments of 0.1
OVERVOLTAGE TRIP
LEVEL:     OFF
OVERVOLTAGE TRIP
DELAY:     2.0 SEC.
Range: 5 - 30%, OFF
Increments of 1
Range: 1.0 - 30.0 SEC.
Increments of 0.1
UNDERVOLTAGE ALARM
LEVEL:     OFF
UNDERVOLTAGE ALARM
DELAY:     1.0 SEC.
Range: 5 - 30%, OFF
Increments of 1
Range: 1.0 - 30.0 SEC.
Increments of 0.1
UNDERVOLTAGE TRIP
LEVEL:     OFF
UNDERVOLTAGE TRIP
DELAY:     2.0 SEC.
Range: 5 - 30%, OFF
Increments of 1
Range: 1.0 - 30.0 SEC.
Increments of 0.1
LINE FREQUENCY TRIP
WINDOW:     DISABLED
LINE FREQUENCY TRIP
DELAY:     1.0 SEC.
Range: 0 - 6, Disabled
Increments of 1
Range: 1.0 - 20.0 SEC.
Increments of 0.1