SP.4 Relay Assignment (Setpoint Page 4)
(Security Level: 2)
All of the protection functions of the TX are user programmable to an
output relay.  The factory will ship with all tripping functions assigned to
TRIP (AUX1) relay, and all alarm functions to ALARM (AUX2) relay.  Note:
AUX1 - 4 are Factory Set and should not be changed.
SP4.1
The following is a list of all the user programmable functions.
Note:  The Relay Assignments are factory defaults.
FUNCTIONS
RELAY  ASSIGNMENT
IMBALANCE TRIP
TRIP (AUX1)
SHORT CIRCUIT TRIP
TRIP (AUX1)
OVERCURRENT TRIP
TRIP (AUX1)
STATOR RTD TRIP
TRIP (AUX1)
NON-STATOR RTD TRIP
TRIP (AUX1)
GROUND FAULT HI SET TRIP
TRIP (AUX1)
GROUND FAULT LO SET TRIP
TRIP (AUX1)
PHASE LOSS TRIP
TRIP (AUX1)
ACCELERATION TIME
TRIP (AUX1)
START CURVE TRIP
TRIP (AUX1)
OVER FREQUENCY TRIP
TRIP (AUX1)
UNDER FREQUENCY TRIP
TRIP (AUX1)
I*I*T START CURVE
TRIP (AUX1)
LEARNED START CURVE
TRIP (AUX1)
PHASE REVERSAL
TRIP
OVERVOLTAGE TRIP
TRIP
UNDERVOLTAGE TRIP
TRIP
POWER FACTOR TRIP
TRIP
TACH ACCEL TRIP
TRIP
INHIBITS TRIP
TRIP
SHUNT TRIP
AUX 3
BYPASS DISCREPANCY
NONE
EXTERNAL  INPUT 1
NONE
EXTERNAL INPUT 2
NONE
DUAL RAMP
NONE
THERMOSTAT
TRIP (AUX 1)
OVERLOAD WARNING
ALARM (AUX2)
OVERCURRENT ALARM
ALARM (AUX2)
GROUND FAULT ALARM
ALARM (AUX2)
UNDERCURRENT ALARM
ALARM (AUX2)
MOTOR RUNNING
NONE
IMBALANCE ALARM
ALARM (AUX2)
STATOR RTD ALARM
ALARM (AUX2)
NON-STATOR RTD ALARM
ALARM (AUX2)
RTD FAILURE ALARM
ALARM (AUX2)
SELF TEST FAIL
TRIP (AUX1)
THERMAL REGISTER
ALARM (AUX2)
U/V ALARM
ALARM
O/V ALARM
ALARM
POWER FACTOR ALARM
ALARM
KW DEMAND ALARM
ALARM
KVA DEMAND ALARM
ALARM
KVAR DEMAND ALARM
ALARM
AMPS DEMAND ALARM
ALARM
TIMED OUTPUT
NONE
RUN DELAY TIME
NONE
AT SPEED
AUX4