Toshiba 48-1250 A Manual Do Utilizador

Página de 96
TOSHIBA - 48
TX  Series
   48 - 1250A
CURVE C VOLTAGE
LEVEL 6:  67%
CURVE C VOLTAGE
LEVEL 7:  82%
CURVE C RAMP
TIME 7: 2 SEC.
CURVE C VOLTAGE
LEVEL 8:  100%
CURVE C RAMP
TIME 6: 2 SEC.
CURVE C CURRENT
LIMIT:  350% FLA
CURVE C RAMP
TIME 8: 2 SEC.
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 200 - 600%
Increments of 10
CUSTOM CURVE C
SP.7 Custom Acceleration Curve (Setpoint Page 7)
(Security Level: 3)
SP7.1
Setpoint Page 7 allows the user to custom
design the acceleration curve (start curve) to the
specific application.  The user can custom
design up to three different curves in the TX.
Only one curve can be active (enabled) at a
time.  Each of the three curves has eight voltage
levels, with corresponding ramp times and a
current limit setting.
Note:  Each successive voltage level must be
programmed to a voltage level equal to or greater
than the previous level. All eight levels of
voltages must be programmed and the eighth
level has been preset at 100%.
• If Custom Accel Curve has been set to curve A, B
or C on this page, the TX will override the Start
Control Mode selected in Setpoint Page 2, (even
if Start Control Mode in Setpoint Page 2 has not
been set to Custom Accel Curve).
Note: Setpoint Page 7 has a security level 3
requirement.