JADE™ ECONOMIZER MODULE
11
62-0331—07
Operation or Use My outdoor temperature 
reading on the STATUS menu is 
not accurate.
Check the sensor wiring. Enthalpy sensors are to be wired to the Sylk Bus terminals. 
Temperature sensors are to be wired to the OAT and MAT terminals. 
If my enthalpy sensor drifts in 
accuracy over time, can I re-
calibrate it? 
The sensors are not able to be re-calibrated in the field. However there is a menu item under 
the ADVANCED menu where you are able to input a limited offset in temperature and 
humidity for each sensor you have connected to the economizer. 
Can I go back to factory 
defaults and start over? 
Under the SYSTEM SETUP menu you can change the setpoints to the factory defaults.
Will I be able to see the LCD 
screen when it is in the unit? 
The LCD screen has a backlight that is always illuminated. 
What is a good setpoint for the 
Mixed Air Temperature (MAT)?
The mixed air temperature is the temperature of air that you want to supply to the space. In a 
commercial building, this is between 50 to 55°F (10 to 13°C). The mixed air is the mixing of 
the return air and the outdoor air. 
I am using enthalpy sensors. 
Why did the control ask me to 
input a dry bulb changeover 
temperature? 
In the event the humidity sensor in the enthalpy sensors fails, the backup algorithm in the 
control is to default to the temperature sensor in the enthalpy sensor. 
In checkout, the outdoor 
damper closes when I 
command it open. 
Check the actuator linkage or rotation. In the CHECKOUT mode, the outdoor damper should 
drive open or closed with the return air damper having the opposite effect. 
How do I set my minimum 
position? 
The minimum position is set using the VENTMIN and VENTMAX setup in the SETPOINTS 
menu. VENTMIN is the minimum ventilation required when using an occupancy sensor and 
VENTMAX is the minimum ventilation when not using an occupancy sensor for Demand 
Control Ventilation. The VENTMAX position is set the same as with the potentiometer on the 
analog economizers and is the output voltage to the damper actuator. The range is 2 Vdc 
closed OA damper and 10 Vdc open OA damper. 
What if my damper does not go 
completely closed in the 
checkout operation?
Check the damper linkage or hub to make sure the damper is able to close completely. 
How do I set the OCC? 
There are two settings for the OCC setting, INPUT and ALWAYS. INPUT is from the space 
thermostat, if it has an occupancy output. ALWAYS is the unit in the occupied mode, if the 
economizer is powered (fan on). 
Does the economizer save my 
program values if the unit loses 
power?
Yes, once the changes are stored in the controller they will be stored until they are changed 
by the operator. 
If the unit is left in checkout, 
how long will the unit stay in 
checkout mode without input?
The unit will remain in checkout for 10 minutes, then return to normal operation.
Table 3. Installation Issues and Concerns. (Continued)
Area
Issue or Concern
Possible Cause and Remedy