PIPE RELIEF VALVE TO OPEN DRAIN.
N O T E :     I F   T E M P E R E D   WAT E R   I S 
RECIRCULATED,  RETURN  LINE  SHOULD 
BE CONNECTED AT POINT “A”.
INSTALL  IN ACCORDANCE  WITH  LOCAL 
CODES.
TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE
WITH OR WITHOUT BUILDING RECIRCULATION
 
DANGER 
TEMPERATURE  SETTING  SHOULD  NOT  EXCEED 
SAFE  TEMPERATURE AT  FIXTURES.  SEE  WATER 
TEMPERATURE  CONTROL  WARNING  ON  PAGE  3.  IF 
HIGHER PREHEAT TEMPERATURES ARE NECESSARY 
TO  OBTAIN ADEQUATE  BOOSTER  OUTPUT, ADD AN 
ANTI-SCALD  VALVE  FOR  HOT  WATER  SUPPLIED TO 
FIXTURES.
CAUTION:  IF BUILDING COLD WATER SUPPLY HAS A 
BACK-FLOW PREVENTER, CHECK VALVE OR WATER 
METER  WITH  CHECK  VALVE  PROVISIONS  FOR 
THERMAL EXPANSION OF WATER IN THE HOT WATER 
SYSTEM  MUST BE PROVIDED.
CAUTION:  IF  THE  PLUMBING 
REQUIRES  THE  USE  OF  PIPES 
WITH DISSIMILAR MATERIAL (FOR 
EXAMPLE, STEEL AND COPPER), 
USE  DIELECTRIC  UNIONS  TO 
PREVENT AN ELECTRO-GALVANIC 
ACTION  BETWEEN  THE  PIPING 
COMPONENTS WITH DISSIMILAR 
MATERIALS.