NOTE  1:  TOGGLE  SWITCH  CONTROLS  180°F  (82°C)    WATER 
CIRCULATION.  INSTALL  ON  OR  CLOSE TO  DISHWASHER. TOGGLE   
SWITCH MUST BE CLOSED (ON) DURING THE RINSE OPERATION AND 
OPEN (OFF) WHEN DISHWASHER IS NOT OPERATING OR WHEN ON 
LONG STANDBY.
NOTE 2: INSTALL LINE TEMPERATURE CONTROL IN AN UNINSULATED 
TEE BEYOND THE DISHWASHER TAKEOFF IN THE SANITIZING LOOP.  
CONTROL SHOULD BE SET AT 185°F (85°C).
NOTE 3: ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE 
DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK.
NOTE  4:  IF TEMPERED  WATER  IS  RECIRCULATED,  RETURN  LINE 
SHOULD BE CONNECTED AT POINT A.
 
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE 
AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON 
PAGE 3. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO 
OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE 
FOR HOT WATER SUPPLIED TO FIXTURES.
CAUTION:    IF  BUILDING  COLD  WATER  SUPPLY  HAS A  BACK-FLOW 
PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE 
PROVISIONS  FOR  THERMAL  EXPANSION  OF  WATER  IN  THE  HOT 
WATER SYSTEM  MUST BE PROVIDED.
*PIPE RELIEF VALVE TO OPEN DRAIN
INSTALL IN ACCORDANCE WITH LOCAL CODES
TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE 
WITH RECIRCULATION OF SANITIZING LOOP
CAUTION:  IF THE  PLUMBING  REQUIRES 
THE  USE  OF  PIPES  WITH  DISSIMILAR 
MATERIAL  (FOR  EXAMPLE,  STEEL AND 
COPPER),  USE  DIELECTRIC  UNIONS  TO 
PREVENT AN ELECTRO-GALVANIC ACTION 
BETWEEN  THE  PIPING  COMPONENTS 
WITH DISSIMILAR MATERIALS.