Commissioning 
 
9.2 Procedure 
 
1FW6 Built-in torque motors 
186
 
Configuration Manual, 05/2009, 6SN1197-0AD00-0BP7 
&KSKDVH8
&KSKDVH:
&KSKDVH9
&K
 
Figure 9-12  Determining the commutation angle offset by measuring the EMF and the standardized 
electrical rotor position via a DAC, with a positive motor direction of rotation 
 
Definition of channels (Ch1 to Ch4): 
Ch1: EMF phase U to neutral point 
Ch2: EMF phase V to neutral point 
Ch3: EMF phase W to neutral point 
Ch4: Standardized electrical rotor position via DAC measuring signal 
 
 
Note 
If you select the measuring signal "Standardized, electrical rotor position", the SHIFT factor 
must be set to 8 and the offset value to – 2.5 V. 
 
When the drive is synchronized, the difference between the EMF phase U and the electrical 
rotor position must not exceed 10°. 
If the difference is greater than this value, the position of the zero mark must be shifted using 
software via MD 1016 "COMMUTATION_ANGLE_OFFSET".