National Instruments Field Point cFP-Al-110 Manual Do Utilizador

Página de 20
FP-AI-110 and cFP-AI-110
2
ni.com
To install the FP-AI-110, refer to Figure 1 and complete the 
following steps:
1. Slide the terminal base key to either position X (used for any 
module) or position 1 (used for the FP-AI-110).
2. Align the FP-AI-110 alignment slots with the guide rails on the 
terminal base.
3. Press firmly to seat the FP-AI-110 on the terminal base. When 
the FP-AI-110 is firmly seated, the latch on the terminal base 
locks it into place.
Figure 1.  Installing the FP-AI-110
Installing the cFP-AI-110
The cFP-AI-110 mounts on a Compact FieldPoint backplane 
(cFP-BP-x), which provides operating power to the module. 
Installing the cFP-AI-110 onto a powered backplane does not 
disrupt the operation of the FieldPoint bank.
To install the cFP-AI-110, refer to Figure 2 and complete the 
following steps:
1. Align the captive screws on the cFP-AI-110 with the holes on 
the backplane. The alignment keys on the cFP-AI-110 prevent 
backward insertion. 
2. Press firmly to seat the cFP-AI-110 on the backplane.
3. Using a number 2 Phillips screwdriver with a shank of at least 
64 mm (2.5 in.) length, tighten the captive screws to 1.1 N
⋅ m 
1
I/O Module
2
Terminal Base
3
Alignment Slot
4
Key
5
Latch
6
Guide Rails
1
3
2
4
5
6