Carrier WEATHERMAKER 8000 58WAV Manual Do Proprietário

Página de 24
2. Humidifier (HUM)
Quick-connect terminal (HUM) and screw terminal (C
OM
-
24V) are provided for 24-v humidifier connection. The termi-
nals are energized with 24-v 0.5-amp maximum after inducer
motor prepurge period.
DO NOT connect furnace control HUM terminal to HUM
(humidifier) terminal on Thermidistat™, Zone Controller or
similar device. See Thermidistat, Zone Controller, thermostat,
or controller manufacturer’s instructions for proper connec-
tion. A failure to follow this warning could result in fire.
NOTE:
A field-supplied, 115-v controlled relay connected to
EAC terminals may be added if humidifier operation is desired
during blower operation.
Step 9—Venting
Refer to the national or local installation code such as NFGC in the
United States or the NSCNGPIC in Canada for proper vent sizing
and installation requirements. Use the enclosed Installation In-
struction (Single-Stage Vent Tables for Category I Fan-Assisted
Furnaces) for a quick, easy reference.
After fully assembling the vent connector to the furnace flue collar,
securely fasten the vent connector to the collar with two field-
supplied, corrosion-resistant, sheet metal screws located 180° apart
and midway up the collar.
The horizontal portion of the venting system shall maintain a
minimum of 1/4-in. upward slope per linear ft and it shall be
rigidly supported every 5 ft or less with hangers or straps to ensure
that there will be no movement after installation.
Table 5—Electrical Data
UNIT SIZE
VOLTS—
HERTZ—
PHASE
OPERATING
VOLTAGE RANGE
MAXIMUM
UNIT AMPS
MINIMUM
WIRE GAGE
MAXIMUM
WIRE LENGTH (FT)‡
MAXIMUM
FUSE OR CKT BKR
AMPS†
Maximum*
Minimum*
045-08
115—60—1
127
104
6.0
14
47
15
045-12
115—60—1
127
104
8.3
14
34
15
070-08
115—60—1
127
104
5.9
14
47
15
070-12
115—60—1
127
104
8.7
14
32
15
091-14
115—60—1
127
104
9.0
14
31
15
091-16
115—60—1
127
104
10.4
14
27
15
111-12
115—60—1
127
104
8.0
14
35
15
111-16
115—60—1
127
104
10.1
14
28
15
111-20
115—60—1
127
104
14.4
12
31
20
136-16
115—60—1
127
104
10.1
14
28
15
136-20
115—60—1
127
104
13.3
12
33
20
155-20
115—60—1
127
104
14.0
12
31
20
* Permissible limits of the voltage range at which the unit operates satisfactorily.
† Time-delay type is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
Fig. 9—Standard Heating and Cooling Application Wiring Diagram
A99440
115-V FIELD-
SUPPLIED
DISCONNECT
AUXILIARY
J-BOX
24-V
TERMINAL
BLOCK
THREE-WIRE
HEATING-ONLY
FIVE WIRE
NOTE 1
NOTE 2
FIELD-SUPPLIED
DISCONNECT
CONDENSING
UNIT
TWO
WIRE
FURNACE
C
O
N
T
R
O
L
R
G
COM
W
C
R
G
Y
GND
GND
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
BLOWER DOOR SWITCH
WHT
BLK
WHT
BLK
NOTES:
Connect Y-terminal in furnace as shown for proper blower operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
W
Y/Y2
GND
THERMOSTAT
TERMINALS
1.
2.
3.
9