TERMINAL STRIP REFERENCE CHART 
D:
  STARTING THE OPERATOR 
#  NAME 
DESCRIPTION 
13  CLOSE EDGE 
Momentary or continuous signal.  
This input is active only when referenced to the closing direction, it 
has no effect on the gate when opening or about to open.  If 
activated when the gate is closing the gate will stop, pause and 
reverse in the open direction for 1/2 second (approx. 2 inches) and 
stop.  Continuous activation will prevent the gate from moving in 
the close direction. Continuous activation while the gate is open 
will prevent the Timer-To-Close function (if enabled) from 
automatically closing the gate.  If a second activation occurs before 
the limit switch is activated the gate will stop and a require a 
renewed, intended input to move in the close direction and before 
an automatic activation device (timer, etc.) will operate. This input 
is intended for Electric Gate Edge systems and other minimum-
contact devices as appropriate.  Connect here and to terminal #16 
COMMON.  Multiple devices may be connected in parallel.  
14  MASTER OPEN 
Momentary or continuous signal.  Master 
(output configuration)  
 
This terminal is used to coordinate two independent systems (two 
control box/mechanical unit combinations controlling separate gate 
leaves).  Connects to terminal #6 (OPEN) in the companion control 
box and controls the direction of movement in the companion box 
(Switch Jumper Position diagram, Figure 19, Page 18).   
15  MASTER CLOSE  Momentary or continuous signal.  Master 
(output configuration)  
 
16  COMMON 
Common connection for low voltage 
signal inputs, terminals 2 through 15. 
This terminal is used to coordinate two independent systems (two 
control box/mechanical unit combinations controlling separate gate 
leaves).Connects to terminal #7 (CLOSE) in the companion control 
box and controls the direction of movement in the companion box 
(Switch Jumper Position diagram, Figure 19, Page 18).  
 
NAME 
DESCRIPTION 
10  CLOSE PHOTO 
Momentary or continuous signal.  
This input is active only when referenced to the closing 
direction, it has no effect on the gate when opening or about to 
open.  If activated when the gate is closing the gate will stop, 
pause and reverse in the open direction for 1/2 second 
(approx. 2 inches) and stop.  Continuous activation will 
prevent the gate from moving in the close direction.  When the 
input is removed normal operation is resumed. . Continuous 
activation while the gate is open will prevent the Timer-To-
Close function (if enabled) from automatically closing the gate.   
This input is intended for photoelectric eye systems and other 
non-contact devices as appropriate.  Connect here and to 
terminal #16 COMMON.  Multiple devices may be connected 
in parallel.  
11  REV LOOP 
Momentary or continuous signal.  
This input is active only when the gate is closing or when it’s 
fully open and the Close Timer is operative.  All stand-alone 
vehicle detectors, photo-eyes and active edges should be 
connected here and to terminals #3 or #13 COMMON.  
Multiple devices may be connected in parallel.  
12  OPEN EDGE 
Momentary or continuous signal.   
This input is active only when referenced to the opening 
direction, it has no effect on the gate when closing or about to 
close.  If activated when the gate is opening the gate will stop, 
pause and reverse in the close direction for 1/2 second 
(approx. 2 inches) and stop. Continuous activation will prevent 
the gate from moving in the open direction.  If a second 
activation occurs before the limit switch is activated the gate 
will stop and a require a renewed, intended input to move in 
the open direction and before an automatic activation device 
(timer, etc.) will operate. This input is intended for Electric 
Gate Edge systems and other minimum-contact devices as 
appropriate.  Connect here and to terminal #16 COMMON.  
Multiple devices may be connected in parallel.  
SETTING THE LIMIT SWITCHES
 
Once the gate arm has been installed to the gate and operator, the 
limit switches can be adjusted and set. BE CERTAIN TO TURN 
THE MAIN POWER SWITCH TO THE OPERATOR “OFF” 
BEFORE PROCEEDING. 
The instructions in this manual describe a right hand gate installation, 
as shown in Figure 10. A right hand gate installation is defined as a 
gate which swings inward and to the right to an open position, with 
the operator on the right, as viewed from inside of the gate area 
facing out. The RS4000 as shipped is configured for a right hand 
installation. If a left hand installation is required, the limit switch 
wires and motor wires must be swapped. This is fully defined in the 
right hand/left hand wiring schematic illustrated in Figure 13. 
Assuming a right hand gate installation, swing the gate to position it a 
few inches short of the fully closed position. In this right hand 
installation, the “closed” gate limit will be located on the left side of 
the output shaft (see Figure 18).   
 
The limit mechanism consists of a spring loaded flipper toggle which 
activates a micro switch. These are installed on a bracket which 
pivots around the output shaft. A trigger pin, installed on the large 
output pulley, is used to flip the toggle and thus activate or de-
activate the micro switch. With this mechanical combination, the 
switching action is positive and precise. This accuracy is not 
diminished by repeated operations of the gate. 
Identify the small trigger pin mounting hole closest to the “close” 
limit located toward the front side of the pulley between the “open” 
and “close” limit brackets. Manually swing the gate open until this 
           WARNING! 
RISK OF ELECTROCUTION 
DO NOT BEGIN TO SET THE FOLLOWING 
ADJUSTMENTS  UNTIL THE POWER IS 
TURNED OFF AT THE TWIST’R CONTROL BOX