9700 SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
v
MITSUBISHI ELECTRIC 9700SERIES UPS
WARNING  2
This UPS does not include a Bypass Input circuit breaker (MCCB).  The
Bypass Input contactor (CB3) does not protect against load induced
short circuits.  The bypass input circuit breaker (MCCB) is field supplied
and installed.  Breaker(MCCB)'s Specifications are as follows:
Capacity (kVA) Bypass Voltage (VAC) Maximum Bypass
Rating (AAC)
Recommended
Breaker (A)
100
208
278
350
100
480
120
150
100
600
96
100
150
208
416
500
150
480
180
225
150
600
144
150
225
208
625
700
225
480
271
300
225
600
217
225
300
480
361
400
300
600
289
300
375
480
451
500
375
600
361
400