1.16
Backup Battery Calculation
• The following table is used to calculate the standby battery
capacity required by NFPA when using the DS7400Xi:
1.17
Standby Current Load
• Battery Ah - (20% Storage + 0.375 Ah Alarm)
• The following table is the derated battery divided by hours minus the control standby (175 mA):
1.15
Max.  Load Currents
  * = Add 15 mA for each additional zone in alarm.
 ** = When calculating Standby and Alarm Current for the Octal Relay Module, use 10 mA plus 40 mA for each activated relay.
*** = Maximum current draw if using the DS7400Xi Panel power supply. Total of all outputs cannot exceed 750 mA.
Rechargeable
Battery Size
Max. Standby
for 4 hours
Max. Standby
for 8 hours
Max. Standby
for 24 hours
Max. Standby
for 48 hours
Max. Standby
for 60 hours
Max. Standby
for 72 hours
Max. Standby
for 80 hours
7 Ah
1.0 A
470 mA
X
X
X
X
X
8 Ah
1.2 A
580 mA
X
X
X
X
X
14 Ah
1.5 A
1.1 A
270 mA
X
X
X
X
15 Ah
1.5 A
1.2 A
300 mA
X
X
X
X
17.2 Ah
1.5 A
1.5 A
380 mA
100 mA
X
X
X
21 Ah
1.5 A
1.5 A
500 mA
160 mA
100 mA
X
X
28 Ah
1.5 A
1.5 A
740 mA
280 mA
190 mA
130 mA
100 mA
30 Ah
1.5 A
1.5 A
800 mA
310 mA
210 mA
150 mA
120 mA
35 Ah
1.5 A
1.5 A
970 mA
400 mA
280 mA
200 mA
170 mA
Device 
Quantity 
Standby Current 
per Device 
Total Standby 
Current 
(Quantity x Standby 
Current per Device) 
Alarm Current  
per Device 
Total Alarm 
Current 
(Quantity x Alarm 
Current per Device) 
DS7400Xi (4+) Control Panel 
175 mA 
175 mA 
250 mA 
250 mA 
DS7416i Advanced Radio Communications Module 
 
127 mA 
 
127 mA 
 
DS7412 - RS232 Serial Interface Module 
 
35 mA max. 
 
35 mA max. 
 
DS7420i -Dual Phone Line/Bell Supervision Module 
 
20 mA 
 
140 mA 
 
DS7430 – Multiplex Expansion Module 
 
65 mA 
 
65 mA 
 
DS7432 – 8-Input Remote Module 
 
10 mA 
 
10 mA 
 
DS7433 – 8-Input Direct Module 
 
65 mA 
 
80 mA* 
 
DS7436 – Dual Multiplex Expansion Module 
 
130 mA 
 
130 mA 
 
DS7445/DS7445i Keypad 
 
75 mA 
 
75 mA 
 
DS7447/ DS7447E Keypad 
 
100 mA 
 
100 mA 
 
DS7448 Keypad 
 
80 mA 
 
100 mA 
 
DS7450, DS7452, DS7455 Contact Points 
 
350 
μ
 
350 
μ
 
DS7457 – Single Zone Multiplex Input Module 
 
350 
μ
 
350 
μ
 
DS7460 – Dual Zone Module 
 
1 mA 
 
1 mA 
 
DS7465 – Input/Output Module 
 
1 mA 
 
1 mA 
 
DS7480 – Bell Supervision Module 
 
7 mA 
 
50 mA 
 
DS7481 – Single Phone Line Monitor 
 
20 mA 
 
20 mA 
 
DS7488 – Octal Relay Module** 
 
10 mA + 40 mA** 
 
10 mA + 40 mA** 
 
DS7489 – Solid State Output Module 
 
10 mA 
 
750 mA max.*** 
 
MX280 Series Multiplex Smoke Detectors 
 
500 
μ
 
560 
μ
 
MX540 (DS7473) PIR Detector 
 
800 
μ
 
800 
μ
 
MX835 TriTech
®
 PIR/Microwave Detector 
 
6 mA 
 
35 mA 
 
MX775 (DS7470) PIR Detector 
 
200 
μ
 
200 
μ
 
MX794 (DS7474) PIR Detector 
 
800 
μ
 
800 
μ
 
MX934 (DS7471) PIR Detector 
 
200 
μ
 
200 
μ
 
MX938 (DS7472) PIR Detector  
 
200 
μ
 
200 
μ
 
MX950 (DS7476) TriTech
®
 PIR/Microwave Detector 
 
6 mA 
 
35 mA 
 
RF3222 Wireless Receivers 
 
30 mA 
 
30 mA 
 
2-Wire Smoke Detectors 
 
 
 
 
 
4-Wire Smoke Detectors 
 
 
 
 
 
Bells, Horns, etc. 
 
 
 
 
 
Other 
Sensors 
 
     
Other 
 
     
  
Grand 
Total 
 
 Grand 
Total 
 
 
 
Max. Load Currents
Standby
Alarm
UL Installations
1.5 A
2.5 A
Maximum Current By Output:
Not to exceed the maximum load currents listed above in Standby or Alarm
Aux. Power & Keypad (Combined)
1.0 A
1.0 A
Option Power
1.0 A
1.0 A
Bell Output
X
1.75 A
Programmable Output 2
500 mA
500 mA
Loop Power +
500 mA
500 mA