Dimensions and Installation Information (in inches) 
Hood Exhaust Duct
Outside ventilation requires a hOOd ExhAuST duCT. 
Read the following carefully.
EXHaUSt CoNNECtIoN
The hood exhaust has been designed to mate with a 
standard 3-1/4” x 10” rectangular duct.
if a round duct is required, a rectangular-to-round 
transition adaptor must be used. do not use less than a 
6” diameter duct.
REaR EXHaUSt
if a rear or horizontal exhaust is to be used, care should 
be taken to align exhaust with the space between studs, 
or wall should be prepared at the time it is constructed 
by leaving enough space between the wall studs to 
accommodate exhaust.
Grille
Filter Kit accessory
Filter Kit
Jx81d–Recirculating 
Charcoal Filter kit
To be used when  
the Advantium oven  
cannot be vented  
to the outside.
maXImUm DUCt LENGtH
For satisfactory air movement, the total duct length of 
3-1/4” x 10” rectangular or 6” diameter round duct should 
not exceed 140 equivalent feet.
ELBoWS, tRaNSItIoNS, WaLL aND RooF CapS, etc., 
present additional resistance to airflow and are equivalent 
to a section of straight duct which is longer than their 
actual physical size. when calculating the total duct 
length, add the equivalent length of all transitions and 
adaptors plus the length of all straight duct sections. The 
chart below shows the approximate feet of equivalent 
length of some typical ducts.
Duct  
Equivalent
a. Rectangular-To-Round 
5 Ft. 
  Transition Adaptor
B. wall Cap 
40 Ft.
C. 90° Round Elbow 
10 Ft.
D. 45° Round Elbow 
5 Ft.
E. 90° Rectangular Elbow 
25 Ft.
F.  45° Rectangular Elbow 
5 Ft.
G. Roof Cap 
24 Ft.