Specifications and Accessories Catalog
Room Freeze Protection: When the unit senses 
temperatures of 40°F or below, the unit activates  
the fan motor and either the electric resistance  
heater or the hydronic heater. 
Easy-to-use Controls: No complex controls to confuse 
your guests and create phone calls for your manager. 
Controls are easy to read, understand, and activate. 
Our new 7-button control panel provides guests with 
complete control of the unit for their in-room comfort 
while maintaining overall energy efficiency.
Easy to Service with On-Board LED Diagnostics:  
The main components are easily serviced and there  
is no guessing to determine the problem with our  
easy-to-read diagnostics. 
Stonewood Room Front: Our Stonewood room front 
strikes the balance between attractive styling and 
practical design. Distinctive contours and a modern 
appearance enhance the character of even the most 
luxurious room, while the sleek 7⅝" depth maximizes 
usable space for your guests.
Remote Thermostat Control: When the DigiSmart™ 
wireless remote thermostat (DS01E, sold separately) is 
set up, both the remote thermostat and unit control 
panel continue to control the unit, providing flexibility 
and home-like system control. Installation requires no 
more than pressing two buttons. No need to run wires 
or make electrical connections. 
Extended Heat Pump Heating: Heat pump models  
will operate in the heating mode down to as low as  
24°F outdoor ambient temperature.
Zero Floor Clearance: The unit can be installed flush  
to a finished floor, if desired. (Some accessories do  
not have zero clearance).
30-Second Fan-Off Delay: The fan continues to run  
30 seconds after the compressor has stopped in either 
cooling or heat pump mode and after electric heat has 
been turned off. This improves efficiency by dispersing 
the conditioned air on the coils into the room.
Compressor Lock-In: This feature helps prolong the life 
of the compressor by preventing short-cycling. When 
the compressor is switched from Off to On because 
room temperature has risen or fallen below the 
specified limit, it will remain on for at least 4 minutes.  
If the temperature set-point is changed during this  
4 minutes, the lock-in feature is overridden.
Automatic Emergency Heat: No more “my unit is not 
heating” complaints during the middle of the night. 
Heat pump units will automatically switch over to 
electric resistance heat if the heat pump compressor 
system fails or if the heating load is greater than the 
unit capacity.
Constant Fan Mode: Take advantage of each unit’s  
dual options — select continuous fan operation or  
cycle the fan ON and OFF with the thermostat.  
Our 7-button design allows guests to select fan 
performance while allowing the owner to have the  
unit revert to the desired program of continuous  
fan or cycle with conditioning.
Hidden Ventilation Control: The ventilation control 
lever is hidden from the occupant's view to allow you  
to manage ventilation requirements.
High-Pressure Switch: Protects the unit from high 
pressure and damage to the unit, helping to ensure 
long unit life.