Premium PIA9066A Manual Do Proprietário

Página de 58
INSTALLATION MANUAL Information for the installer
MODEL     capacity (Btu/h)
5k     
7k     
9k     
12k      15/18k      22/24k      28/30k     
Liquid pipe diameter
Gas pipe diameter
 Lenght of pipe with standard charge
Maximum distance between indoor and outdoor unit
Additional gas charge
Max. diff. in level between indoor and outdoor unit 
Type of refrigerant(1)
 1/4
( 6)
    3/8
(
9.52)
 1/4
( 6)
 1/4
( 6)
 1/4
( 6)
 1/4
( 6)
    3/8
(
9.52)
    3/8
(
9.52)
    1/2
  (
12)
    1/2
  (
12)
    3/8
(
9.52)
    3/8
(
9.52)
     5/8
(
15.88)
     5/8
(
15.88)
3m
3m
3m
3m
4m
4m
4m
15m
15m
15m
15m
15m
15m
15m
20g/m
20g/m
20g/m
20g/m
30g/m
30g/m
30g/m
5m
5m
5m
5m
5m
5m
5m
R22 
R22 
R407C
R22 
R407C
R22 
R407C
R22 
R407C
R22 
R407C
R22 
R407C
 (1)  Refer to the data rating label sticked on the outdoor unit.
TIGHTENING TORQUE FOR PROTECTION CAPS AND FLANGE CONNECTION 
22
MODEL     capacity (Btu/h)
7k     
9k     
12k      15/18k      22/24k      28/30k     
Liquid pipe diameter
Gas pipe diameter
 Lenght of pipe with standard charge
Maximum distance between indoor and outdoor unit
Additional gas charge
Max. diff. in level between indoor and outdoor unit 
Type of refrigerant(1)
 1/4
( 6)
 1/4
( 6)
 1/4
( 6)
 1/4
( 6)
    3/8
(
9.52)
    3/8
(
9.52)
    1/2
  (
12)
    3/8
(
9.52)
    3/8
(
9.52)
     5/8
(
15.88)
     5/8
(
15.88)
3m
3m
3m
4m
4m
4m
15m
15m
15m
15m
15m
15m
20g/m
20g/m
20g/m
30g/m
30g/m
30g/m
5m
5m
5m
5m
5m
5m
R410A
R410A
R410A
R410A
R410A
R410A
MODEL     capacity (Btu/h)
9k     
12k      15/18k      22/24k     
Liquid pipe diameter
Gas pipe diameter
Lenght of pipe with standard charge
Maximum distance between indoor and outdoor unit
Additional gas charge
Max. diff. in level between indoor and outdoor unit 
Type of refrigerant(1)
 1/4
( 6)
 1/4
( 6)
 1/4
( 6)
    3/8
(
9.52)
    1/2
  (
12)
    1/2
  (
12)
    3/8
(
9.52)
     5/8
(
15.88)
3m
3m
4m
4m
15m
15m
15m
15m
20g/m
20g/m
30g/m
30g/m
5m
5m
5m
5m
R22 
R410A
R22 
R410A
R22 
R410A
R22 
R410A
PIPE
 1/4
( 6)
    3/8
(
9.52)
    1/2
  (
12)
     5/8
(
15.88)
TIGHTENING TORQUE
[N x m]
TIGHTENING TORQUE
[N x m]
CORRESPONDING STRESS
(using a 20 cm wrench)
15 - 20
31 - 35
35 - 45
75 - 80
Service port nut
Protection caps
7 - 9
25 - 30
wrist strength
arm strength
arm strength
arm strength
INVERTER TYPE
    3/8
(
9.52)
FIXED-SPEED  TYPE
FIXED-SPEED  TYPE