PowerLogic ION7550 / ION7650 Installation Guide
© 2007 Schneider Electric. All rights reserved.
21
COM1 SETUP
PROTOCOL
The communications protocol
ION, Modbus RTU, Modbus
Master, DNP V3.00,
GPS:Truetime/Datum,GPS:
Arbiter, GPS:Arbiter-Vorne,
Factory, Ethergate, ModemGate
ION
BAUD RATE
The data rate, in bits per second
300
1
, 1200, 2400, 4800, 9600,
19200, 38400, 57600, 115200
19,200
TRAN DELAY
The transmit delay in seconds
0 to 1
0.010
UNIT ID
Every meter on an RS-485 network
must have a unique Unit ID number 1 to 9999
From serial
number
number
2
SERIAL PORT
Parity and stop bits for the port
8N1, 8N2, 8E1, 8E2, 8O1, 8O2 8N1
MODE
Hardware mode for the port
RS232 or RS485
RS232
FLOW CONTROL Specifies the handshake mode
when COM1 is set to RS232
RTS + DELAY or RTS/CTS
RTS +
DELAY
RS485 BIAS
Turns on biasing when Mastering
on the RS-485 bus
ON or OFF
OFF
CO
M2 SETUP
PROTOCOL
The communications protocol
See COM1 protocol
ION
BAUD RATE
The data rate, in bits per second
300
1
, 1200, 2400, 4800, 9600,
19200, 38400, 57600, 115200
19,200
TRAN DELAY
The transmit delay in seconds
0 to 1
0.010
UNIT ID
Every meter on an RS-485 network
must have a unique Unit ID number 1 to 9999
101
SERIAL PORT
Parity and stop bits for the port
8N1, 8N2, 8E1, 8E2, 8O1, 8O2 8N1
RS485 BIAS
Turns on biasing when Mastering
on the RS-485 bus
ON or OFF
OFF
COM
3
SETUP
PROTOCOL
The communications protocol
ION, Modbus RTU, Modbus
Master, DNP V3.00,
GPS:Truetime/Datum,GPS:
Arbiter, GPS:Arbiter-Vorne,
Factory
ION
BAUD RATE
The data rate, in bits per second
300
1
, 1200, 2400, 4800, 9600,
19200, 38400, 57600, 115200
19,200
TRAN DELAY
The transmit delay in seconds
0 to 1
0.010
UNIT ID
Every meter on an RS-485 network
must have a unique Unit ID number 1 to 9999
102
ANSWER HR
RINGS
The number of rings during defined
answer hours
0 to 255
1
NON-ANSWER
HR RINGS
The number of rings during defined
non-answer hours
0 to 255
5
COM4 SETUP
PROTOCOL
The communications protocol
ION, Modbus RTU, DNP V3.00,
Factory
ION
BAUD RATE
The data rate, in bits per second
1200, 2400, 4800, 9600,
19200
9600
TRAN DELAY
The transmit delay in seconds
0 to 1
0.010
UNIT ID
Every meter on an RS-485 network
must have a unique Unit ID number 1 to 9999
103
SERIAL PORT
Parity and stop bits for the port
8N1, 8N2, 8E1, 8E2, 8O1, 8O2 8N1
Menu
Setting
Description
Range (Values)
Default