Description of the I/O Modules 
Excel 800 
EN1B-0410GE51 R0908A 
 
22
Analog Input Modules 
Types of Analog Input Modules 
Table 25. Excel 800 Analog Input Modules 
type 
description 
housing 
XF821 
Panel Bus Analog Input Module  light-gray 
XFL821 
L
ON
W
ORKS
 Bus Analog Input 
Module 
dark-gray 
XS821-822 terminal 
socket 
light-gray 
 
Features 
•  8 analog inputs 
•  Sensor-break and short-circuit detection, see section 
"Troubleshooting" on page 31. 
 
 
Fig. 35. XF821AU Analog Input Module with terminal 
socket 
Legend 
 1  Service button S1 
  2  Hex switch S2 
 3  Service LED 
 4  Power LED 
 
Functionality of service LED and power LED: see Table 42 
and following. 
 
Terminals 
25 26
74
78
73
77
72
76
71
75
24
V~
24
V~
24
V~0
24
V~0
COM
B
COM
B
COM
A
COM
A
AI8
8
AI7
7
AI6
6
AI5
5
AI4
4
AI3
3
AI2
2
AI1
1
18
17
16
15
14
13
12
GND
11
GND GND GND GND GND GND GND
22
V
21
10
GND
9
GND
AUX
V
AUX
 
Fig. 36. Terminal assignment and internal connections of 
Analog Input Modules 
 
Table 26. Description of Analog Input Module terminals 
ter-
minal 
signal 
comment 
71, 75 
COM a 
2-wire communication bus 
(LON/Panel Bus) 
72, 76 
COM b 
2-wire communication bus 
(LON/Panel Bus) 
73, 77 
24 V~ 
Power supply 
74, 78 
24 V~0 
Power supply 
1 ─ 8 
AI1 ─ AI8  Analog inputs 1 ─ 8 
9 ─ 18 
GND 
Ground. All grounds are connected 
internally to each other 
21, 22 
10 VDC / 
5 mA 
Auxiliary voltage signal (used e.g. for 
supplying setpoint potentiometers). 
Connections to these terminals 
must be made in the same room.
 
25, 26 
 
Shield connection (functional earth), 
internally connected to the DIN rail 
 
NOTE: 
Shield connection to be used for shielded I/O 
cables only. It is not allowed to connect a 
L
ON
W
ORKS
 shield.