Sanyo UHX2452 Manual Do Utilizador

Página de 114
1-3
Test Run
1
2
3
4
5
6
7
8
YES
Make necessary corrections.
Check the alarm 
contents.
Check the alarm contents.
Turn OFF the indoor and 
outdoor unit power.
NO
YES
NO
*1
*2
*3
*3
*2
CASE 1
CASE 2
CASE 3B
CASE 3A
YES
YES
NO
YES
NO
NO
NO
YES
YES
NO
Recheck the items to check before the test run.
Have the outdoor sub units been connected?
Are the inter-unit control wires 
connected to more than 1 refrigerant 
system?
Is it possible to turn ON the power only 
for the 1 refrigerant system where the 
test run will be performed?
Will automatic address setting be 
performed in Heating mode?
Is it OK to start the compressors?
Turn ON the indoor and 
outdoor unit power.
Short-circuit the mode change pin 
(CN101) on the outdoor main unit PCB. 
At the same time, short-circuit the 
automatic address pin (CN100) for 1 
second or longer, then release it.
Short-circuit the automatic address 
pin (CN100) on the outdoor main 
unit PCB for 1 second or longer, 
then release it.
Short-circuit the automatic address pin (CN100) 
on the outdoor main unit PCB for 1 second or 
longer, then release it.
Start indoor and outdoor unit 
cooling operation.
LED 1 and 2 blink alternately.
Start indoor and outdoor unit 
heating operation.
LED 1 and 2 blink alternately.
LED 1 and 2 blink alternately 
(about 2 or 3 minutes).
Is it OK to start the compressors?
Turn ON the indoor and 
outdoor unit power.
Turn OFF the indoor 
and outdoor unit 
Turn ON the indoor and 
outdoor unit power for that 
refrigerant system only.
Are LED 1 and 2 on the 
outdoor unit PCB OFF?
Are LED 1 and 2 on the 
outdoor unit PCB OFF?
Set the unit address.
Set the No. of outdoor units.
Set the No. of indoor units.
Set the system address.
When multiple outdoor main units exist, disconnect the terminals 
extended from the shorted plugs (CN003) at all outdoor main unit 
PCBs except for 1.
Alternatively, move the sockets to the OPEN side.
<Outdoor unit control PCB>
Unit No. setting switch
(S007)
<Outdoor unit control PCB>
Unit No. setting switch
(S006)
<Outdoor unit control PCB>
Unit No. setting switch
(S004 and S005)
<Outdoor unit control PCB>
Unit No. setting switch
(S002 and S003)
(Check the link wiring.)
*1
  The unit with the unit 
No. set to 1 is the 
main unit. All other 
units are sub units.
Note:  It is not necessary to remove 
the socket that is used to short-
circuit the terminal plugs from 
the outdoor sub unit PCBs.
Refer to "Table of Self-
Diagnostic Functions and 
Description of Alarm Displays."
*2  A minimum of 5 hours must have passed after the 
power was turned ON to the outdoor unit.
*3  All indoor units operate in all refrigerant systems 
where the power is ON.
Check that test run preparation is OK.
(Do not allow the short-circuited pins to remain short-circuited.)
Refer to the remote 
controller test-run 
settings.
Set the wired remote controller for test run.
Does system operate?
Return remote control to normal mode
Check and make corrections according to
"Table of Self-Diagnostic Functions."
End test run.
Make necessary 
corrections
1. Test  Run
2. Test Run Procedure
Items to Check Before the Test Run
1.  Turn the remote power switch on at least 5 hours before 
the test, in order to energize the crankcase heater.
2.  After performing the leak inspection, applying vacuum, 
and performing refrigerant charge for the tubing which 
is connected on-site, fully open the outdoor unit service 
valve. However if only one outdoor unit is installed, a 
balance tube is not used. Therefore, leave the valve fully 
closed.
3.  When replacing the control PCB, be sure that the settings 
on the new PCB match those on the old PCB.
4.  Use caution when making the settings. If there are dupli-
cated system addresses, or if the settings for the Nos. of 
the indoor units are not consistent, an alarm will occur 
and the system will not start.
5.  These settings are not made on the indoor unit PCB.
SM830157_W-2WAY_ECO-i.indb   3
SM830157_W-2WAY_ECO-i.indb   3
2007/06/08   14:23:12
2007/06/08   14:23:12