DESCRIPTION 
 
The Network Communications Module (NCM) is an Asynchronous Data Module designed for use in 
RFL IMUX 2000 T1 and E1 multiplexers. It provides one DCE Half/Full-Duplex channel between an 
unlimited number of locations using a single 64 kbps DS0 time slot. The NCM provides a fast and 
reliable NMS communication path between nodes of a T1 or E1 network, and can also be used for 
party-line applications such as DNP and Modbus networking. 
 
The NCM is remote-controllable when installed in an RFL remote controllable shelf. The following 
module parameters can be configured remotely via NMS or locally via DIP switches. A DIP switch 
setting selects whether the card is in remote or local mode. 
 
 
TX/RX 
Time 
Slot 
   1-31 
TX Bus Direction 
 
 
 
TX-A(RX-B) / TX-B(RX-A) 
Service 
enable/disable 
   On/Off 
Equipment 
Loopback 
   On/Off 
Payload 
Loopback 
   On/Off 
Block timeslot 16 for CAS in E1 operation  On/Off 
Port 
     On/Off 
Rogue 
Control 
    On/Off 
CM Address   
 
 
 
Any, Greater Than, Less Than 
Baud Rate 
 
 
 
 
2400, 4800, 9600, 19.2k, 38.4k 
Parity 
     None, 
Odd, 
Even, 
Mark, 
Space 
Word Length   
 
 
 
7 or 8 data bits 
Application Modes 
 
 
 
Broadcast, NMS, Master, D&I slave, End slave 
Remote 
Operation 
   On/Off 
RFL NCM 
 
RFL Electronics Inc. 
November 6, 2007 
                         1 