Honeywell MS4103 Manual Do Utilizador

Página de 268
89
Non-Spring Return Direct Coupled Actuator
ml6174; ml7174
S
ubmitt
al Sheet
S
ML6174; ML7174
Used to control dampers in 
applications such as variable air 
volume (VAV) terminal units and for 
mounting on ball valves; suitable 
for use with SPDT or floating 
thermostats or building automation 
controls.
SPECIFICATIONS
Actuator Type  ....................................... Damper
Rotational Stroke  .................................. 90 degrees
Fail Safe Mode  ..................................... Non-Spring Return
Rated Torque ........................................ 70 lb-in. (8 Nm) 
External Auxiliary Switches Available  .. Yes, 201052B
Electrical Connections  ......................... Screw terminals
Environmental Rating  ........................... NEMA1
Feedback  ............................................. With accessory
Frequency  ............................................ 50 Hz, 60 Hz
Manual operation  ................................. Declutch mechanism
Mounting  .............................................. Direct Coupled
Maximum Noise Rating, 
Driving (dBA @ 1m) .............................. 45
Timing, Nominal Driving at 60 Hz ......... 90 sec., 180 sec. or 420 sec.
Power Consumption, Driving ................ 2.4 VA or 5.4 VA
Rotation to Open  .................................. By wiring
Rotational Stroke Adjustment  ............... Mechanically limited at 45 or 
60 degrees in cw or ccw 
directions
Compatible Damper Shafts .................. 3/8 to 1/2 in. square or round
(10 to 13 square/round) 
Shaft Adapter Type  .............................. Aluminum Hub, two set screws
Supply Voltage  ..................................... 24 Vac ±20%
Materials ............................................... Steel plate and Plenum rated 
plastic
Operating Humidity Range (% RH) ...... 5 to 95% RH, non-condensing
Ambient Temperature Range  ............... 20 F to 125 F (-18 C to 50 C) 
Storage Temperature Range  ................ 20 F to 130 F (-18 C to 54 C) 
Weight  .................................................. 1.5 lb (0.68 kg) 
Includes ................................................ 4074ENY Bag Assembly
APPROVALS
Underwriters Laboratories, Inc. ............ UL873, Plenum Rated
Canadian Underwriters 
Laboratories, Inc.  ................................. cUL C22.2 No. 24-93
FEATURES
• Control for air damper applications with up to 20 sq.ft. 
assuming 3.5 lb-in. per sq.ft. of damper area, velocity 
independent. 
• Magnetic coupling eliminates the need for mechanical 
stops or limit switch adjustments by limiting stall torque to 
130 lb-in. maximum. 
• Mount directly on 3/8 to 1/2 in. round and square damper 
shafts. All models include manual declutch lever for ease of 
mounting, and bag assembly with two minimum position 
setscrews. 90 second timing models are suitable for use 
with pressure independent VAV systems. 
• Selectable 45, 60, and 90 degree stroke in either clockwise 
or counterclockwise direction.
DIMENSIONS DIAGRAMS
1
(25)
M22990
OPTIONAL
AUXILIARY
SWITCH
T1
T2
-
+
+
24 Vac
2-10 Vdc
4-20 mA
4-7/8
(123)
4-1/4
(108)
5-9/16
(141)
11/16
(18)
1/8
(3)
5/16 (8)
1-11/16
(43)
3-3/8 (86)
1/8
(3)
15/32 (12)
1-5/16
(33)
3 (76)
2-7/8 (73)
1-11/16
(42)
1/8
(3)
1 (25)
M18016
CW
COM
CCW
OPTIONAL
AUXILIARY
SWITCH
11/16
(18)
3-3/8 (86)
4-1/4
(108)
4-7/8
(123)
2-7/8  (73)
1-11/16
(42)
1/8
(3)
1-5/16
(33)
7/8
(22)
2-1/2  (64)
M18018
5-7/8
(149)
1-13/16
(46)
1
(25)
3-5/8  (92)
1-13/16  (46)
3 IN. (76 MM)
MINIMUM SPACING
REQUIRED 
FOR REMOVING 
CONDUIT COVER
3-3/4  (95)
7/8
(22)