“C” Group: Intelligent Terminal Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–44
Input Function Summary Table – This table shows all twenty-four intelligent input 
functions at a glance. Detailed descriptions of these functions, related parameters and 
settings, and example wiring diagrams are in 
Input Function Summary Table
Option
Code
Terminal 
Symbol
Function Name
Description
00
FW
Forward Run/Stop
ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Stop Mode, motor stops
01
RV
Reverse Run/Stop
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
02
CF1 *1
Multi-speed Select, 
Bit 0 (LSB)
ON
Binary encoded speed select, Bit 0, logical 1
OFF
Binary encoded speed select, Bit 0, logical 0
03
CF2
Multi-speed Select, 
Bit 1
ON
Binary encoded speed select, Bit 1, logical 1
OFF
Binary encoded speed select, Bit 1, logical 0
04
CF3
Multi-speed Select, 
Bit 2
ON
Binary encoded speed select, Bit 2, logical 1
OFF
Binary encoded speed select, Bit 2, logical 0
05
CF4
Multi-speed Select, 
Bit 3 (MSB)
ON
Binary encoded speed select, Bit 3, logical 1
OFF
Binary encoded speed select, Bit 3, logical 0
06
JG
Jogging
ON
Inverter is in Run Mode, output to motor runs at 
jog parameter frequency
OFF
Inverter is in Stop Mode
07
DB
External DC Braking ON
DC braking will be applied during deceleration
OFF
DC braking will not be applied
08
SET
Set (select) 2nd 
Motor Data
ON
The inverter uses 2nd motor parameters for 
generating frequency output to motor
OFF
The inverter uses 1st (main) motor parameters 
for generating frequency output to motor
09
2CH
2-stage Acceleration 
and Deceleration
ON
Frequency output uses 2nd-stage acceleration 
and deceleration values
OFF
Frequency output uses standard acceleration and 
deceleration values
11
FRS
Free-run Stop
ON
Causes output to turn OFF, allowing motor to 
free run (coast) to stop
OFF
Output operates normally, so controlled deceler-
ation stops motor
12
EXT
External Trip
ON
When assigned input transitions OFF to ON, 
inverter latches trip event and displays E12
OFF
No trip event for ON to OFF, any recorded trip 
events remain in history until Reset