Hitachi L200 Manual Do Utilizador

Página de 280
Using Intelligent Output Terminals
Oper
ations
and Monitor
ing
4–42
Alarm Signal
The inverter alarm signal is active when a fault has 
occurred and it is in the Trip Mode (refer to the 
diagram at right). When the fault is cleared the 
alarm signal becomes inactive.
We must make a distinction between the alarm 
signal AL and the alarm relay contacts [AL0], 
[AL1] and [AL2]. The signal AL is a logic 
function, which you can assign to the open collec-
tor output terminals [11] or [12] or the relay 
outputs. The most common (and default) use of the relay is for AL, thus the labeling of 
its terminals. Use an open collector output (terminal [11] or [12]) for a low-current logic 
signal interface or to energize a small relay (50 mA maximum). Use the relay output to 
interface to higher voltage and current devices (10 mA minimum).
Run
Stop
Trip
Fault
Fault
Alarm signal active
STOP
RESET
STOP
RESET
RUN
Option 
Code
Terminal 
Symbol
Function Name
Output 
State
Description
05
AL
Alarm Signal
ON
when an alarm signal has occurred and has not 
been cleared
OFF
when no alarm has occurred since the last 
clearing of alarm(s)
Valid for outputs:
11, 12, AL0 – AL2
Required settings:
C026, C036
Notes:
By default, the relay is configured as normally 
closed (C036=01). Refer to the next page for an 
explanation.
In the default relay configuration, an inverter power 
loss turns ON the alarm output. the alarm signal 
remains ON as long as the external control circuit 
has power.
When the relay output is set to normally closed, a 
time delay of less than 2 seconds occurs after 
powerup before the contact is closed.
Terminals [11] and [12] are open collector outputs, 
so the electric specifications of [AL] are different 
from the contact output terminals [AL0], [AL1], 
[AL2].
This signal output has the delay time (300 ms 
nominal) from the fault alarm output.
The relay contact specifications are in 
contact diagrams for different conditions are on the 
next page.
RY
+
Example for terminals [AL0], [AL1], [AL2] 
(default output configuration shown—
see page 
Relay position 
shown is for 
normal opera-
tion (no alarm).
Example for terminal [11] or [12] (requires 
output configuration—see page 
AL0
AL2
AL1
Inverter logic 
circuit board
Inverter output 
terminal circuit
See I/O specs 
on page 
.
AL
AL
Load
Power
supply
12 11
CM2