Hitachi L200 Manual Do Utilizador
ModBus Data Listing
Appendix B
B–22
D001
Output frequency
monitor
monitor
R
Real-time display of output
frequency to motor, from
0.0 to 400.0 Hz
frequency to motor, from
0.0 to 400.0 Hz
00Ah
0 to
4000
0.1 Hz
D002
Output current monitor
*1
*1
R
Filtered display of output
current to motor (100 ms
internal filter time constant),
range is 0 to 200% of inverter
rated current
current to motor (100 ms
internal filter time constant),
range is 0 to 200% of inverter
rated current
00Bh
0 to
2000
0.1%
D003
Rotation direction
monitor
monitor
R
Three different indications:
00... Stop
01... Forward
02... Reverse
00... Stop
01... Forward
02... Reverse
00Ch
0, 1, 2
—
D004
(high)
Process variable (PV),
PID feedback monitor
PID feedback monitor
R
Displays the scaled PID
process variable (feedback)
value (A075 is scale factor),
range is 0.00 to 99900
process variable (feedback)
value (A075 is scale factor),
range is 0.00 to 99900
00Dh
0 to
999900
0.00%
times
const.
D004
(low)
R
00Eh
D005
Intelligent input
terminal status
terminal status
R
Displays the state of the intelli-
gent input terminals [x],
Bit 0 = [1] to Bit 7 = [6]
gent input terminals [x],
Bit 0 = [1] to Bit 7 = [6]
00Fh
0 to 63
—
D006
Intelligent output
terminal status
terminal status
R
Displays the state of the intelli-
gent output terminals [x],
Bit 0 = [11], Bit 1 = [12],
Bit 2 = [AL]
gent output terminals [x],
Bit 0 = [11], Bit 1 = [12],
Bit 2 = [AL]
0010h
0 to 7
—
D007
(high)
Scaled output frequency
monitor
monitor
R
Displays the output frequency
scaled by the constant in B086.
Decimal point indicates range:
0.00 to 99999
scaled by the constant in B086.
Decimal point indicates range:
0.00 to 99999
0011h
0 to
999999
0.01 Hz
times
const.
D007
(low)
R
0012h
D013
Output voltage monitor
R
Voltage of output to motor,
range is 0.00 to 200.00%
range is 0.00 to 200.00%
0013h
0 to
20000
0.01%
D016
(high)
Cumulative operation
RUN time monitor
RUN time monitor
R
Displays total time the inverter
has been in RUN mode in
hours.
Range is 0 to 999000
has been in RUN mode in
hours.
Range is 0 to 999000
0014h
0 to
999999
1 hour
D016
(low)
R
0015h
D017
(high)
Cumulative power-on
time monitor
time monitor
R
Displays total time the inverter
has been in RUN mode in
hours.
Range is 0 to 999000
has been in RUN mode in
hours.
Range is 0 to 999000
0016h
0 to
999999
1 hour
D017
(low)
R
0017h
D080
Trip counter
R
Number of trip events,
range is 0 to 65535
range is 0 to 65535
0018h
0 to
65535
1 trip
event
event
D081
Trip monitor 1
R
Displays trip data
0019h
—
—
D082
Trip monitor 2
R
Displays trip data
001Ah
—
—
D083
Trip monitor 3
R
Displays trip data
001Bh
—
—
List of Holding Registers
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.