Hitachi L200 Manual Do Utilizador

Página de 280
L200 Inverter Specifications
Getting Star
ted
1–10
General Specifications
The following table applies to all L200 inverters.
Item
General Specifications
Protective housing  *1
IP20
Control method
Sinusoidal Pulse Width Modulation (PWM) control
Carrier frequency
2kHz to 14kHz (default setting: 5kHz)
Output frequency range  *4
0.5 to 400 Hz
Frequency accuracy
Digital command: 0.01% of the maximum frequency
Analog command: 0.1% of the maximum frequency (25
°C ± 10°C)
Frequency setting resolution
Digital: 0.1 Hz; Analog: max. frequency/1000
Volt./Freq. characteristic
V/f optionally variable, V/f control (constant torque, reduced torque)
Overload capacity
150% of rated current for 1 minute
Acceleration/deceleration time
0.01 to 3000 seconds, linear and S-curve accel/decel, second
accel/decel setting available
Input
signal
Freq.
setting
Operator panel
Up and Down keys / Value settings
Potentiometer
Analog setting
External signal  
*9
0 to 10 VDC (input impedance 10k Ohms), 4 to 20 mA (input 
impedance 250 Ohms), Potentiometer (1k to 2k Ohms, 2W)
FWD/
REV 
Run
Operator panel
Run/Stop (Forward/Reverse run change by command)
External signal
Forward run/stop, Reverse run/stop
Intelligent input
terminal
FW (forward run command), RV (reverse run command), CF1~CF4 
(multi-stage speed setting), JG (jog command), DB (external 
braking), SET (set second motor), 2CH (2-stage accel./decel. 
command), FRS (free run stop command), EXT (external trip), USP 
(startup function), SFT (soft lock), AT (analog current input select 
signal), RS (reset), TH (thermistor thermal protection), STA (start), 
STP (stop), F/R (forward/reverse), PID (PID disable), PIDC (PID 
reset), UP (remote control up function), DWN (remote control down 
function), UDC (remote control data clearing), OPE (operator 
control), ADD (ADD frequency enable), F-TM (force terminal 
mode)
Output
signal
Intelligent output 
terminal
RUN (run status signal), FA1,2 (frequency arrival signal), OL 
(overload advance notice signal), OD (PID error deviation signal), 
AL (alarm signal), Dc (analog input disconnect detect), FBV (PID 
two-stage control output), NDc (network detection signal), LOG 
(logic output)
Frequency monitor
PWM output; Select analog output frequency monitor, analog output 
current monitor or digital output frequency monitor
Alarm output contact
ON for inverter alarm (1C contacts, both normally open or closed 
avail.)