Basic Parameter Settings
These settings affect the most fundamental behavior of the inverter—the outputs to the 
motor. The frequency of the inverter’s AC output determines the motor speed. You may 
select from three different sources for the reference speed. During application develop-
ment you may prefer using the potentiometer, but you may switch to an external source 
(control terminal setting) in the finished application, for example.
The base frequency and maximum frequency settings interact according to the graph 
below (left). The inverter output operation follows the constant V/f curve until it reaches 
the full-scale output voltage at the base frequency. This initial straight line is the 
constant-torque part of the operating characteristic. The horizontal line over to the 
maximum frequency serves to let the motor run faster, but at a reduced torque. This is the 
constant-power operating range. If you want the motor to output constant torque over its 
entire operating range (limited to the motor nameplate voltage and frequency rating), 
then set the base frequency and maximum frequency equal as shown (below right).
NOTE: The “2nd motor” settings in the tables in this chapter store an alternate set of 
parameters for a second motor. The inverter can use the 1st set or 2nd set of parameters 
to generate the output frequency to the motor. See 
Base
 Frequency
Maximum
 Frequency
Base frequency = 
maximum frequency
V
V
100%
100%
f
f
Constant torque
0
0
A003
A004
A003
A004
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
A003 Base frequency setting
Settable from 30 Hz to the 
maximum frequency
50.0
60.0
Hz
F-BASE   00060Hz
A203 Base frequency setting, 
2nd motor
Settable from 30 Hz to the 2nd 
maximum frequency
50.0
60.0
Hz
2F-BASE  00060Hz
A004 Maximum frequency 
setting
Settable from the base 
frequency up to 400 Hz
50.0
60.0
Hz
F-MAX    00060Hz
A204 Maximum frequency 
setting, 2nd motor
Settable from the 2nd base 
frequency up to 400 Hz
50.0
60.0
Hz
2F-MAX   00060Hz