GP Series Portable Chillers 
Chapter 6: Troubleshooting 
41 of 73 
Problem 
Possible cause 
Solution 
Pump running in reverse. 
Verify rotation; if running in reverse 
rotation, reverse any two main power 
leads. Re-verify for correct pump 
rotation. 
Pump process pressure low (refer 
to curves for normal pressure for 
various pumps). 
Check for foreign matter. 
Clean the system strainer. 
Pump process pressure is too high. 
Restricted water flow. 
Check for partially closed valves etc. 
Make sure that all lines are properly 
sized. 
Clean filters. 
Restricted condenser air flow. 
Clean condenser. 
Unit low on refrigerant. 
Check the refrigerant charge by viewing 
sight glass on liquid line upstream of the 
expansion valve. 
Compressor not operating 
efficiently. 
Call service. 
Unit runs continuously, but not 
enough cooling power
.
 
Unit under-sized for application. 
Call sales rep.