Liebert 3000 Manual Do Utilizador

Página de 76
Operation with Advanced Microprocessor Controls
6
2.4.4 Run Hours Log
The total operating hours of all major components in the unit can be monitored from the display and 
are retained in nonvolatile memory. Run times are available for the following:
• Compressor
• GLYCOOL Coil (or CW Coil as used on Dual Cooling Unit)
• Fan
• (HUM) humidifier
• (RH1) reheat 1 (or Hot Water or SCR Reheat)
• (RH2) reheat 2
The component run hours for each individual component can be reset by selecting the run hours dis-
play screen for the desired component, then pressing ENTER within 5 minutes of applying power to 
the control. The user will then be prompted to press ENTER to clear the selected component's run 
hours.
2.4.5 Analog Sensors
The four (4) analog sensor inputs can be monitored from the display. The inputs are filtered, then dis-
played along with the text label assigned during setup. See Analog Setup on page 11.
2.5
Setpoints/Setup
Selecting Setpoints/Setup from the Main Menu will display the following selections:
• View setpoints
• Setup system
• Run diagnostics
• Change passwords
2.5.1 View Setpoints
Control and alarm setpoints can be reviewed and/or changed through the display. The following table 
lists the default setpoints and their allowable ranges.
NOTE
Run hours for a component should be reset ONLY when the component has been replaced.
NOTE
Setpoints and system setup parameters are kept in nonvolatile memory.
Table 1
Default setpoints and ranges
Setpoint
Default
Range
Temperature Setpoint
72
°
F
40 to 90
°
F (5 to 32
°
C)
Temperature Sensitivity
2.0
°
F
1 to 9.9
°
F (0.6 to 5.6
°
C)
Humidity Setpoint
50%
20 to 80% RH
Humidity Sensitivity
5%
1 to 30% RH
High Temperature Alarm
80
°
F
35 to 95
°
F (2 to 35
°
C)
Low Temperature Alarm
65
°
F
35 to 95
°
F (2 to 35
°
C)
High Humidity Alarm
60%
15 to 85% RH
Low Humidity Alarm
40%
15 to 85% RH