2-40 HP Portable Chillers 
Chapter 4: Operation 
35 of 70 
4-2 Start-up 
1.  Turn on the chiller and put it under a process load. 
2.  Set the controller for the To Process temperature you want, using the Up 
Arrow button or the Down Arrow button located on the face of the controller. 
3.  Adjust the High/Low thermostat, located in the electrical enclosure, to 8°F 
(4.4ºC) below the To Process temperature you want. The High/Low 
thermostat is factory-set at 42ºF (6ºC). See page 36 for information on 
resetting the High/Low thermostat. 
4.  Check the pump amp draw and pump pressure. Make sure that the amp draw 
reading is within the running load and service factor amps. 
5.  Operate the chiller, looking for any leaks and listening for unusual noises or 
vibrations that could indicate improper operation. 
Note: 
Elevated sound level and substantially reduced current draw indicate reverse 
rotation. After several minutes of operation, the compressor internal protector 
trips. 
4-3  Setting the Process Water Temperatures 
Chiller Controller 
To change the process water temperature set point, press the Up Arrow button to raise the set 
point, and press the Down Arrow button to lower the set point. 
4-4 Auto-Tuning 
E5CK Controller Only 
The Auto-Tune function lets you fine-tune the control PID to process requirements. Activate 
the Auto-Tune function whenever the process under control changes. Don’t be alarmed by 
control response. It may take the process temperature above and below the set points as many 
as three times before leveling off and controlling the process set point. Auto-Tuning can take 
up to 45 minutes and is best done before any product is being run. 
1.  Press and hold down the AT key for several seconds until the AT indicator 
flashes. 
2.  When the AT LED light stops flashing, the controller is tuned and ready for 
operation. 
Eurotherm 3216 Controller 
1.  Press the INDEX key once.  “A. Tune” will be displayed. 
2.  Press the UP arrow once to display “on”. 
3.  Press the MODE key once to running condition.  The top display will flash 
“tune”.  The tune is complete when the display stops flashing. 
 
4-5 Optional 
Communications 
The communications function allows you to monitor and set controller parameters by a 
program prepared and running on a host computer connected to the controller. 
When using the communications function, you must add on the unit for RS-232C or RS-485 
serial communications. The controller communications function allows you to read/write 
parameters, do operating instructions, and select the setting level.