2-40 HP Portable Chillers 
Chapter 6: Troubleshooting 
42 of 70 
Problem 
Possible cause 
Solution 
Plugged Y-Strainer 
Clean 
Hot gas not coming on 
Replace relay board on control bed hot 
gas coil 
Pump runs, compressor cycles at 
short intervals. 
Low water flow 
Install bypass between to-and-from 
process line 
 
Water/glycol mixture inadequate 
for process. 
Make sure that the water/glycol mixture 
protection is right for the process. 
Defective or improperly set 
High/Low thermostat. 
Adjust or replace. 
Refrigerant low pressure switch is 
set too high. 
Call service to adjust pressure control. 
Water temperature is too high. 
Refrigerant charge is low. 
Call service to find and repair the leak, 
then have refrigerant added. 
Pump running in reverse. 
Verify rotation; if running in reverse 
rotation, reverse any two main power 
leads. Re-verify for correct pump 
rotation. 
Pump pressure low (refer to curves 
for normal pressure for various 
pumps). 
Check for foreign matter. 
Clean the system. 
Pump pressure is too high. 
Restricted water flow. 
Check for partially closed valves etc. 
Make sure that all lines are properly 
sized. 
Restricted condenser air. 
Clean filters. 
Clean condenser. 
Unit low on refrigerant. 
Check the refrigerant charge. 
Compressor not operating 
efficiently. 
Call service. 
Unit runs continuously, but not 
enough  cooling power. 
Unit under-sized for application. 
Call sales rep.