2-40 HP Portable Chillers 
Chapter 7: Appendix 
63 of 70 
7-6  Typical Ductwork for Air-Cooled Chillers 
 
*See specification tables on pages 45-48 for air flow and pressure capacities. 
When locating your air-cooled portable chiller and designing its ductwork, note any potential high 
temperature conditions when discharging into your building and any negative pressures with the building 
when discharging air outside. 
Notes: 
• Customer use of ductwork requires the high pressure fan option for models 5 through 15 hp. • 
Allow 30” (77 cm) minimum clearance around the chiller footprint to facilitate free passage of cooling air 
and service accessibility 
• Size the ductwork for maximum capacity • Support ductwork from the 
building structure, not off of the chiller 
• Back draft damper to outside must be closed at all times when 
fan/blower is not operating 
• Chillers with dual fans/blower must have a back draft damper on the cycling 
fan/blower to prevent recirculation of hot discharge air 
• Chillers are designed to operate at a condensing 
entering air temperature of 60ºF (16ºC) minimum 
• Maximum total static pressure drop external to the 
chiller must not exceed 0.30” WG (75 pa)