Hoshizaki 73183 Manual Do Utilizador

Página de 42
13
b) Freezer
1. Startup/Cool Down 
MH and PH energize. There is a slight delay before cabinet temperature or 
high-temperature alarm (Hi) appears on DM and Comp, ConFM, and EvapFM energize.  
2. Cool Down Achieved 
CM monitors cooling of the cabinet via CTh. CTh cools to 3
°
F (1.7
°
C) below setpoint. 
EvapFM, MH, and PH continue. Comp and ConFM de-energize.
3. Cool Down Restart 
CTh warms to 3
°
F (1.7
°
C) above setpoint. EvapFM, MH, and PH continue. Comp and 
ConFM energize.
4. Defrost
"dEF" is displayed during defrost. There is a 5-minute minimum defrost time and a 1-hour
maximum defrost time.  
a) Temperature/Time Initiation: DTh cools to 32
°
F (0
°
C), then a 4-hour cumulative Comp 
run timer starts. Once 4-hour cumulative Comp run timer terminates and DTh is at or 
below 32
°
F (0
°
C), defrost begins. DH energizes, MH and PH continue, Comp, ConFM, 
and EvapFM de-energize.  
b) Manual Initiation: Manual defrost may be initiated by pressing and holding the lower 
button until "dEF" appears on DM. MH and PH continue. DH energizes, Comp, ConFM,
and EvapFM de-energize.
c) Termination 
(1) After Temperature/Time Initiation: DTh warms to 59
°
F (
15°
C). 3-minute Comp 
delay timer starts, 8-minute EvapFM delay timer starts, and 13-minute temperature 
display delay timer starts. MH and PH continue, DH de-energizes. 
3-minute Comp delay timer terminates. Comp and ConFM energize. 5 minutes 
later, 8-minute EvapFM delay timer terminates and EvapFM energizes. 5 minutes 
after EvapFM energizes, 13-minute temperature display delay timer terminates and 
cabinet temperature returns to DM.
(2) After Manual Initiation: DTh warms to 59°F (15°C). MH and PH continue, DH 
de-energizes. 3-minute Comp/EvapFM delay timer starts, 13-minute temperature 
display delay timer starts.  
3-minute Comp/EvapFM delay timer terminates. Comp, ConFM, and EvapFM 
energize. 10 minutes later, 13-minute temperature display delay timer terminates 
and cabinet temperature returns to DM.
Note: There is a 4-hour minimum defrost interval.
Legend: 
CM–control module; Comp–compressor; ConFM–condenser fan motor;  
CTh–cabinet thermistor; DH–defrost heater; DM–display module; DTh–defrost 
thermistor; 
EvapFM–evaporator fan motor; MH–mullion heater; PH–perimeter 
heater