Hoshizaki 73183 Manual Do Utilizador

Página de 42
19
2. Alarm Safeties
Alarm signals are designed to protect the unit and food product. These alarms give 
information or warnings in the event the unit is operating out of acceptable parameters. 
Should one of the alarms occur, follow the instructions in the table below to address the 
alarm. The alarm code flashes once every second with audible alarm. To silence the 
alarm, press and release the upper button.
Alarm Signals
Alarm Code Problem
Corrective Action/Reset Details
E1
Cabinet Thermistor Malfunction Alarm 
 
Cabinet thermistor has failed.
Cabinet thermistor disconnected, shorted, or open. 
Check connection and continuity. Reconnect or 
replace as needed. 
Unit cycles 5 min. on, 5-min. off.
E2
 
Defrost Thermistor Malfunction Alarm
 
Defrost thermistor has failed.
Defrost thermistor disconnected, shorted, or open. 
Check connection and continuity. Reconnect or 
replace as needed.
Unit cycles on and off with cabinet thermistor.
UHi
High-Voltage Alarm (135VAC
±
5% or 
more)
The compressor de-energizes if voltage protection 
operates. The voltage safeties automatically reset 
when voltage is corrected.
ULo
Low-Voltage Alarm (96VAC
±
5% or less)
Hi
High-Temperature Alarm
Note: When power is turned on, the 
2-hour high-temperature alarm timer is 
bypassed. Therefore, a high-temperature 
alarm can occur at startup.
Refrigerator: Cabinet temperature has 
exceeded the setpoint temperature by 
10°F (5.6°C) for more than 2 hours.
Freezer: Cabinet temperature has 
exceeded the setpoint temperature by 
27°F (15°C) for more than 2 hours.
First try obvious corrections such as closing doors 
and cleaning the condenser.
Automatically resets when temperature returns to 
normal.
Lo
Low-Temperature Alarm
Refrigerator & Freezer: Cabinet 
temperature has remained below the 
setpoint temperature by 8°F (4.4°C) for 
more than 2 hours.
Automatically resets when temperature returns to 
normal.
E13 
Communication Error Alarm
Communication between the control 
module and the display module has been 
interrupted or disconnected.
Check the connections at the control module 
and the display module. If connections are good, 
the control module and display module must be 
replaced. 
The unit operates on a set 5-minutes on, 5-minutes 
off cycle until communication is restored.
"– – –"
Compressor Off
Unit (compressor) off.
 
Press and hold the upper and lower buttons until the 
temperature appears on the display.