G. Installation of Remote Condenser Unit
 WARNING
• Installation of remote condenser unit must be performed by properly trained and 
EPA-certified service personnel.
• The remote condenser unit must be installed in accordance with applicable 
national, state, and local codes and regulations.
• Failure to install the remote condenser unit within these guidelines may adversely 
affect safety, performance, component life, and warranty coverage.
• Power supply and ground wire to the remote condenser unit are supplied from the 
icemaker. For details, see section "II.G.6. Electrical Connection."
1. Location
NOTICE
• The remote condenser unit is intended for outdoor use. Normal operating ambient 
temperature should be within -20°F to +122°F (-29°C to +50°C). Operation of the 
remote condenser unit, for extended periods, outside of this normal temperature 
range may affect icemaker performance.
• The maximum line length for the standard line sizes and refrigerant charge is 
66 feet (20 m). With larger line sizes and/or additional refrigerant, the maximum 
line length is 100 feet (30.5 m). For details, see "II.G.4 Line Set Size and 
Refrigerant Charge."
• The maximum vertical distance between the remote condenser unit and the 
icemaker is 33 feet (10 m) above or 10 feet (3 m) below the icemaker. These 
distances are measured fitting to fitting. See Fig. 9.
The remote condenser unit must be positioned in a permanent site under the following 
guidelines:
• A firm and flat site.
• A dry and well ventilated area with 24" (61 cm) clearance at front and rear for proper air 
circulation and ease of maintenance and/or service should they be required. See Fig. 10.
Fig. 9
Min. 24" (61 cm) Clearance
Air
Air
Fig. 10
Icemaker 
Remote 
Condenser 
Unit 
Service Loop
Max.  
33 Feet 
(10 m)
Remote 
Condenser 
Unit 
Max.  
10 Feet 
(3 m)
Icemaker 
Service Loop