(iv) After Step (iii), de-energize the unit and confirm that the Defrost Timer is in the
minimum position.  Disconnect the resistor from the Controller Board, and energize
the unit.
After the 1 minute water supply cycle, the defrost cycle starts.
Re-connect a 1.5 k
Ω
 - 3.5 k
Ω
 resistor to the Connector K3 (pins #1 and #2) after
the first 2 minutes of the defrost cycle.
        The unit should start the freeze cycle after 1 minute ± 5 seconds from the resistor
         connection.
3) Check the Controller Board by using test program of the Controller Board.
The Output Test Switch “S3” provides a relay sequence test.  With power OFF, place S3
ON and switch power to ICE.  The correct lighting sequence should be none, 2, 3, 4, 1,
and 4, normal sequence every 5 seconds.  S3 should remain in the “OFF” position for
normal operation.
After the 1 minute ± 5 second water supply cycle and the 2 minute ± 10 second defrost
cycle, the unit should start the freeze cycle.
 (ii) After the above step (i), disconnect the Float Switch leads from the Controller Board
within the first 5 minutes of the freeze cycle.
The unit should go into the defrost cycle after the first 5 minutes ± 20 seconds of the
freeze cycle.
(iii) Reconnect the Float Switch Connector to the Controller Board.  After the first 5
minutes of the freeze cycle, disconnect the Float Switch leads from the Controller
Board.
At this point, the unit should start the defrost cycle.