Honeywell DR4300 Manual Do Utilizador

Página de 262
DR4300 Circular Chart Recorder 
92 
DR4300 Circular Chart Recorder Product Manual 
12/03 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
INP EU  
 
NONE [factory setting] 
 
CuFt 
GAL 
CuMt 
LITR 
AcFt 
HMTR 
ENGINEERING UNITS OF INPUT SIGNAL 
NONE—Disables EU conversions and disables TOT EU and 
TOT DP functions. 
Cubic Feet 
Gallons 
Cubic Meters 
Liters 
Acre-Feet 
Hectare-Meters 
RATE  
 
 
SEC  [factory setting] 
MIN 
HOUR 
DAY 
MDAY 
RATE OF INTEGRATION
—This parameter is used to select 
the desired rate of integration. 
SECOND
—EU (Engineering Units) per second 
MINUTE
—EU per minute 
HOUR
—EU per hour 
DAY
—EU per DAY 
MDAY—
Millions of units per day 
TOT EU  
 
NONE [factory setting] 
CuFt 
GAL 
CuMt 
LITR 
AcFt 
HMTR 
ENGINEERING UNITS OF TOTALIZED VALUE 
NONE—Disables EU conversions. 
Cubic Feet 
Gallons 
Cubic Meters 
Liters 
Acre-Feet 
Hectare-Meters 
TOT DP  
8888 [factory setting] 
888.8 
88.88 
TOTALIZED VALUE DECIMAL PLACES
—This parameter is 
used to select the number of decimal places of the displayed 
TOTAL value. This selection will be overridden if the SCALER 
selection is not equal to 1. 
SCALER 
 
 
 
 
1 (displays as E0) 
[factory setting]
 
10 (displays as E1) 
100 (displays as E2) 
1000 (displays as E3) 
1E4 (displays as E4) 
1E5 (displays as E5) 
1E6 (displays as E6) 
1E7 (displays as E7) 
1E8 (displays as E8) 
TOTALIZER SCALE FACTOR
—The totalizer displays the 
current totalized flow value (up to six digits maximum). The 
scaling factor selected here is applied to the totalized value 
when it is displayed. 
 
 
 
 
 
1E4 equals 1 times 10 
4
 (10,000) 
1E5 equals 1 times 10 
5
 (100,000) 
1E6 equals 1 times 10 
6
 (1,000,000) 
1E7 equals 1 times 10 
7
 (10,000,000) 
1E8 equals 1 times 10 
8
 (100,000,000)