DR4300 Circular Chart Recorder 
228 
DR4300 Circular Chart Recorder Product Manual 
12/03 
Step Press 
Action/Result 
Cooling Tuning 
 DISP
 
until you see 
Lower Display
  S2   nnn
 
Display Setpoint 2. 
 
or 
 
Until the value of Setpoint 2 is at the desired value within the 
Cooling zone. 
 DISP
 
until you see 
Lower Display
  UseSP1
 
 
 
or 
 
to toggle to. 
Lower Display
  UseSP2
 
10 
 DISP
 
until you see 
Lower Display
  TuneOF
 
 
11 
 
or 
 
to toggle to 
Lower Display
  TuneON
 Tuning will begin and the lower display will flash 
“TUNING”.  The output will cycle between 0 % 
and 50 % (or low output limit).  When tuning has 
been completed the lower display will again show 
“TuneOF”. The Cool tuning parameters are 
entered for the second set of PID constants in the 
tuning set up group.