Emerson Process Management 3-9000-522 Manual Do Utilizador

Página de 516
MODBUS TEST 
10-7
MON2000
JULY 2010
 Getting Modbus Data
10.3
GETTING MODBUS DATA
Use the following steps to read or write register 
contents to the GC Controller (or any other 
device). See the following subsections for 
additional details. 
Before retrieving data, print a PC Config 
) and check the 
Communication data for variable names 
assigned to the Modbus registers.
1. In the Slave Addr data field, type the Comm 
ID of the GC unit (or other device). WinMB 
will accept a slave address of 1 to 247.
Enter “0” to use the broadcast mode. In the 
broadcast mode, WinMB polls all known 
devices. Each device interprets this message 
as an instruction to read and take action; 
however, a response message may not be 
received by WinMB.
To access previous 
settings, use the spin 
arrows to view and select.
Any change is applied to the 
corresponding register value at 
each device. 
shows which function codes 
support the broadcast mode.