 INSTALLATION AND SETUP
MON2000
Modem Initialization Strings/Setup
JULY 2010
Interpretation of the AT commands for that 
particular modem was as follows:
• \N0 = normal mode; no error control; data 
is buffered (versus ‘direct mode,’ ‘reliable 
mode,  ’or ‘auto reliable mode’)
• \C0 = disable auto reliable buffer (versus 
‘buffer data for 4 seconds or 200 characters’)
• \Q0 = disable flow control (versus ‘enable 
XON/XOFF flow control,’ ‘enable unilateral 
CTS flow control,’ or ‘enable bilateral CTS/
RTS flow control’)
U.S. Robotics Sportster
The following setup for U.S. Robotics Sportster 
28.8 Kbps external FAX-modems was verified 
at the GC assembly and checkout lab:
• At the GC Controller, the modem DIP 
switches were set to 5 and 8 UP, the rest 
DOWN.
• At the PC, the modem DIP switches were 
set to 2, 4, 6, and 7 UP, the rest DOWN.