BACnet Communications - Thermal Management Products
271
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 87
Liebert HPC
™
- Binary Data
Controller Liebert iCOM
®
v4
Data Label
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes
Compressors
Compressor Not Stopping
Compressor Not Stopping
Binary_Value
1
5263_1
RD
Active on Alarm
1, 2
Compressor Superheat Over Threshold
Binary_Value
2
5604_1
RD
Active on Alarm
2
Compressors - Compressor 1
Compressor Hours Exceeded
Compressor Hours Exceeded
Binary_Value
12
5269_1_1
RD
Active on Alarm
1, 2
Compressor High Head Pressure
Binary_Value
13
5270_1_1
RD
Active on Alarm
1, 2
Compressor Low Suction Pressure
Binary_Value
14
5271_1_1
RD
Active on Alarm
1, 2
Compressor Thermal Overload
Binary_Value
15
5272_1_1
RD
Active on Alarm
1, 2
Compressor Low Oil Pressure
Binary_Value
16
5273_1_1
RD
Active on Alarm
1, 2
Compressor Loss of Differential Pressure
Binary_Value
17
5275_1_1
RD
Active on Alarm
1, 2
Compressor Capacity Reduced
Binary_Value
18
5513_1_1
RD
Active on Alarm
1, 2
Compressor Capacity Normal
Binary_Value
19
5773_1_1
RD
Active on Alarm
2
Compressor Contactor Issue
Binary_Value
20
5774_1_1
RD
Active on Alarm
2
Compressors - Compressor 2
Compressor Hours Exceeded
Compressor Hours Exceeded
Binary_Value
29
5269_1_2
RD
Active on Alarm
1, 2
Compressor High Head Pressure
Binary_Value
30
5270_1_2
RD
Active on Alarm
1, 2
Compressor Low Suction Pressure
Binary_Value
31
5271_1_2
RD
Active on Alarm
1, 2
Compressor Thermal Overload
Binary_Value
32
5272_1_2
RD
Active on Alarm
1, 2
Compressor Low Oil Pressure
Binary_Value
33
5273_1_2
RD
Active on Alarm
1, 2
Compressor Loss of Differential Pressure
Binary_Value
34
5275_1_2
RD
Active on Alarm
1, 2
Compressor Capacity Reduced
Binary_Value
35
5513_1_2
RD
Active on Alarm
1, 2
Compressor Capacity Normal
Binary_Value
36
5773_1_2
RD
Active on Alarm
2
Compressor Contactor Issue
Binary_Value
37
5774_1_2
RD
Active on Alarm
2
Compressors - Compressor 4
Compressor Hours Exceeded
Compressor Hours Exceeded
Binary_Value
263
5269_1_4
RD
Active on Alarm
2
Compressor High Head Pressure
Binary_Value
264
5270_1_4
RD
Active on Alarm
2
Compressor Low Suction Pressure
Binary_Value
265
5271_1_4
RD
Active on Alarm
2
Compressor Thermal Overload
Binary_Value
266
5272_1_4
RD
Active on Alarm
2
Compressor Low Oil Pressure
Binary_Value
267
5273_1_4
RD
Active on Alarm
2
Compressor Loss of Differential Pressure
Binary_Value
268
5275_1_4
RD
Active on Alarm
2
Compressor Capacity Reduced
Binary_Value
269
5513_1_4
RD
Active on Alarm
2
Compressor Capacity Normal
Binary_Value
270
5773_1_4
RD
Active on Alarm
2
Compressor Contactor Issue
Binary_Value
271
5774_1_4
RD
Active on Alarm
2
Condenser 1
Condenser Fan Issue
Condenser Fan Issue
Binary_Value
46
5277_1
RD
Active on Alarm
1, 2
Low Condenser Refrigerant Pressure
Binary_Value
47
5278_1
RD
Active on Alarm
1, 2
Condenser Max Fan Speed Override
Binary_Value
48
5545_1
RD
Active on Alarm
1, 2
Condenser 2
Condenser Fan Issue
Condenser Fan Issue
Binary_Value
59
5277_2
RD
Active on Alarm
1, 2
Low Condenser Refrigerant Pressure
Binary_Value
60
5278_2
RD
Active on Alarm
1, 2
Condenser Max Fan Speed Override
Binary_Value
61
5545_2
RD
Active on Alarm
1, 2
Condenser 4
Condenser Fan Issue
Condenser Fan Issue
Binary_Value
67
5277_4
RD
Active on Alarm
2
Low Condenser Refrigerant Pressure
Binary_Value
68
5278_4
RD
Active on Alarm
2
Fluid
Low Fluid Pressure
Low Fluid Pressure
Binary_Value
72
5280_1
RD
Active on Alarm
1, 2
Return Fluid Temp Sensor Issue
Binary_Value
73
5295_1
RD
Active on Alarm
1, 2