Operation 
2-2 
HP Uninterruptible Power System R1500 XR Models User Guide 
continued
 
Item Description 
Meaning/Function 
Utility LED (
Flashing Red—Utility input voltage is outside the +20% to -30% 
configured nominal range. 
Green—Utility voltage is present and output is on, or utility voltage has 
returned to the voltage range for which the UPS has been configured 
(UPS is supplying utility power and the audible alarm should be reset).
Flashing Green—Utility voltage is present and the UPS is in Standby 
mode. Output is off. Batteries charge if needed. 
Overload LED 
Red—UPS load exceeds maximum power available. 
76% to 100% load 
Green—UPS load approximately 76% to 100% of maximum power. 
51% to 75% load 
Green—UPS load approximately 51% to 75% of maximum power. 
26% to 50% load 
Green—UPS load approximately 26% to 50% of maximum power. 
10 
0% to 25% load 
Green—UPS load approximately 0% to 25% of maximum power. 
11 
Configure Mode On 
LED 
Green—UPS is in Configure mode (seen when front bezel removed). 
12 
Configure button 
Places the UPS in Configure mode (seen when front bezel removed). 
13 Test/Alarm 
Reset 
button 
Resets alarms or initiates self-tests. 
14 
Standby button 
Places the UPS in Standby mode (turns output load segments off). 
15 On button 
Starts UPS powering the load. 
Modes of Operation 
The UPS has three modes of operation: 
•  Standby Mode 
—  No power is available at the UPS output receptacles. 
—  The UPS charges the batteries as necessary. 
•  Operate Mode 
—  Power is available at the UPS output receptacles. 
—  The UPS charges the batteries as necessary. 
•  Configure Mode 
—  Power is available at the UPS output receptacles. 
—  The UPS charges the batteries as necessary. 
—  The UPS configuration can be updated.