Specifications 
C-4 
HP Uninterruptible Power System R1500 XR Models User Guide 
Battery Specifications 
 
Table C-5:  Battery Specifications 
Feature Specification 
Type 
Sealed lead-acid; maintenance-free 
Voltage 
48 V Battery String 
Charging 
HP recommends 24 hours to allow full charge 
 
Less than 3 hours to 90 percent capacity at default nominal utility voltage and no load 
Environmental Specifications 
 
Table C-6:  Environmental Specifications 
Feature Specification 
Operating temperature 
10
o
C to 40
o
C (50
o
F to 104
o
F) 
UL-tested at 25
o
C (77
o
F) 
Non-operating temperature 
0
o
C to 25
o
C (32
o
F to 77
o
F) 
Operating humidity 
20% to 80% relative humidity (non-condensing) 
Non-operating humidity 
5% to 95% relative humidity (non-condensing);  
38.7
 o
C (101.7
o
F) maximum wet bulb temperature with no 
cosmetic damage 
Operating altitude 
Up to 2,000 meters (6,562 feet) above sea level 
Non-operating altitude 
Up to 9,144 meters (30,000 feet) above sea level 
Audible noise 
Less than 46 dBA