Emerson Process Management 3410 Manual Do Utilizador

Página de 398
 Reference, Installation, and Operations Manual
Section 3: Installation
3-9000-743 Rev S
June 2013
Series 100 Option Board analog output switch settings
 83
3.5.4
Series 100 Option Board analog output switch settings
The Option Board provides a 4-20 mA analog output signal that is hardware configurable to 
either sink or source current as described in 
 below and in Daniel 
drawing DE-21056 (particularly page 3, notes 26 and 27, 
). 
Table 3-37  Series 100 Option board Analog Out sink setting
Board
Switch
Position
Series 100 Option
S14-1
SINK
S14-2
SINK
S14-3
SINK
Table 3-38  Series 100 Option board Analog Out source setting
Board
Switch
Position
Option
S14-1
SRC
S14-2
SRC
S14-3
SRC
If the analog output is configured for ‘Source’ mode (i.e., powered by the meter), then it 
must be at the bottom of the loop (stack).