Roberts Gorden HE15UT Manual Do Utilizador

Página de 82
SECTION 3: C
LEARANCES
 T
O
 C
OMBUSTIBLES
9 of 73
NOTE:
1.  All dimensions are from the surfaces of all tubes, couplings, tees, elbows and crosses.
2.  Clearances B, C and D can be reduced by 50% after 7500 mm of tubing downstream
from the burner.
3.  All measurements are in millimeters.
4.  Add 60 mm clearance to uncovered u-tube.
FIGURE 14: U-TUBE, OPPOSITE 45° TILT
 Mo
del
 HE1
5
U  
 HE20UT
 HE25UT
 HE30UT
 HE35UT
 HE40UT
 HE45UT
 HE50UT
A
200
200
200
250
250
275
300
300
B
1370
1530
1530
1630
1780
1830
1880
1930
C
1500
1650
1650
1860
1960
2040
2110
2160
D
560
560
560
560
560
560
560
560
A
C
D
B
FIGURE 15: U-TUBE, PROTECTIVE GRILLE
 Model
 HE1
5
UT 
 HE20UT
 HE25UT
 HE30UT
 HE35UT
 HE40UT
 HE45UT
 HE50UT
A
150
150
150
150
150
150
200
200
B
890
970
970
1020
1170
1220
1270
1380
C
1580
1730
1730
1910
1980
2050
2110
2210
D
760
940
940
1000
1090
1150
1200
1300
A
C
D
B
FIGURE 16: U-TUBE, VENTING
 Model
 HE1
5
UT    
 HE
20
UT
 HE
25
UT
 HE
30
UT
 HE
35
UT
 HE
40
UT
 HE
45
UT
 HE
50
UT
E
1000
1000
1000
1000
1000
1000
1000
1000
F
500
500
500
500
500
500
500
500
Radiant tubes
Fan
Unvented
Vented
E
F