Sterling 882.000254.00 Manual Do Utilizador

Página de 91
7/50D Plus or 7/50D Controller 
Chapter 7:  Troubleshooting 
80 
Chapter 7:  Troubleshooting 
7-1 General 
Troubleshooting 
Problem Possible 
cause Solution 
The controller panel is not 
plugged in. 
Plug in the controller panel. 
The external disconnect 
(recommended) in the dedicated 
circuit is open (off). 
Close the switch (on). 
Fuse/circuit breaker in the power 
drop is blown/tripped. 
Replace/reset. 
The controller panel doesn’t light 
up at all. 
Broken controller power switch. 
Replace. 
The motor circuit breaker/ 
overload has tripped. 
Reset the circuit breaker and 
check the motor for the proper 
amp draw on tag. 
Main fuse in power drop circuit 
breaker has blown. 
Replace the fuse/reset circuit 
breaker. 
A pump package doesn’t run, 
even though it is on line and its 
indicator is lit. 
Motor contact is faulty. 
Repair or replace as required. 
The bin below it is full if its 
amber indicator light is off. 
Normal operation. When the 
level drops, material conveys to 
the hopper. 
The hopper is off line. 
Using the controller, place the 
hopper on line. 
The field-installed station bypass 
switch is simulating a Bin Full 
condition. 
Normal operation. Set the switch 
so the hopper is back in the 
loading sequence. 
A vacuum hopper is being 
bypassed in the loading cycle. 
The field-installed station bypass 
switch is bad or mis-wired. 
Repair, replace, or rewire. 
Conveying times are too long 
(Time Fill mode only). 
Time the hopper(s) during 
loading, and set conveying times 
to a few seconds less. 
Vacuum hoppers are over-filling.  Maximum conveying times are 
too long and/or the controller 
does not recognize the Hopper 
Full proximity switch(es). 
Check proximity sensors for 
proper operation. Repair as 
needed. Reset the conveying 
times to a reasonable value, and 
adjust as needed. 
Power supply shorting out. 
Repair shorting circuit. 
Controller blows fuses. 
Improper fuse installed. 
Replace fuse with one that has a 
proper rating.