DS1/T1 CPE loopback jack
555-233-116
156
Issue 4   October 2002 
Configurations using fiber multiplexers
Use the loopback jack when customer premises DS1 wiring connects to an on-site 
fiber multiplexer (MUX) and allows wiring to the network interface point on the 
MUX to be remotely tested. For a G700 Media Gateway, this requires that the 
MM710 CSU be set so it can be used on DS1 wiring to the MUX.
Fiber MUXs can take the place of Interface termination feeds as shown in 
 through 
. Test these spans using the same procedures as 
metallic spans. Note the following points:
1. Fiber MUXs may have loopback capabilities that can the service provider 
can activate from the CO end. These may loop the signal back to the CO or 
back to the DS1 board. If the MUX provides the equivalent of a line 
loopback on the “problem” DS1 facility, activate it after a successful 
loopback jack test, and use it to isolate problems to the wiring between the 
loopback jack and the MUX.
2. Be aware that there are installations that use repeatered metallic lines 
between the MUX and the “dumb” block. These lines require DC power for 
the repeaters and this DC power is present at the “dumb” block interface to 
the CPE equipment. A loopback jack is required in this configuration to 
properly isolate and terminate the DC power
.
To check for the presence of DC, make the following 4 measurements at the 
network interface jack:
1. From transmit tip (T, Pin 5) to receive tip (T1, Pin 2)
2. From transmit ring (R, Pin 4) to receive ring (R1, Pin 1)
3. From transmit tip (T, Pin 5) to transmit ring (R, Pin 4)
4. From receive tip (T1, Pin 2) to receive ring (R1, Pin 1)
All measurements should read 0 (zero) volts DC. For pin numbers and pin 
designations, refer to Integrated Channel Service Unit (ICSU) Installation and 
Operation
.